To determine the damper setpoint position, perform the
following procedure for each condition setpoint, with
mechanical cooling OFF:
Calculate the appropriate supply air temperature using the
following formula:
TS = (TO x Vbz/CFM) + TR x (CFM – Vbz)/CFM
TS = Supply Air Temperature
TO = Outdoor Air Temperature
Vbz = Design Maximum Ventilation CFM
CFM= Unit Supply Airflow Rate
TR = Return Air Temperature
As an example:
Unit Airflow Rate at High Speed is 4000 CFM
Ventilation CFM at design occupancy Vbz is 1200 CFM
TO = 60 F
TR = 75 F
Required TS = 60 x (1200/4000) + 75 x (4000 – 1200/4000)
= 60 x 0.30 + 75 x 0.70 = 18.0 + 52.5
= 70.5
At the W7220 keypad, enter the parameter SETUP - - >
VENTMAX H and adjust the setpoint value until the
observed Supply Air Temperature (MA TEMP) reaches
70.5. Press the
"Enter" key to save this setpoint to
controller memory.
OCCUPANCY
TERMINALS
Fig. 55 - - Integrated Staging Control (ISC) Board - - Occupancy Terminals and Jumper
When determining VENTMIN setpoints, substitute the
value for Va in place of Vbz in the formula.
DCV Setpoint: The SETPOINTS parameter DCV SET
defines the space CO
level above which the DCV mode
2
begins to open the outside air damper beyond its
VENTMIN ventilation lower limit. This setpoint should
be a minimum of 100 ppm greater than the outdoor
ambient CO
level to ensure the outside air will be
2
capable of diluting the space CO
for outdoor CO
is 400 ppm; adjust the setpoint DCV SET
2
to 500 ppm if outdoor CO
factory default value for DCV SET is 1100 ppm.
Economizer Occupancy Control —
The 24- - v signal that terminates at the W7220's OCC
input to place the economizer control in Occupied mode
when the supply fan starts is routed through the rooftop
unit's
Integrated
Staging
OCCUPANCY jumper. To implement an occupancy
control for the economizer operation, connect a contact
set at ISC OCCUPANCY quick- - connect terminals and cut
jumper JMP1. To allow automatic occupancy mode, close
the control contacts. To place the economizer in
Unoccupied mode, open the control contacts.
43
level. A typical value
2
level is not known. The
2
Control
Board
at
CUT JUMPER JMP1
TO IMPLEMENT
OCCUPANCY
CONTROL
C13674