Operation
Listing of all Trouble at 14:35:20 Oct 09, 20XX:
TROUBLE IN 29-41 14:34:22 Oct 09, 20XX
#7 [custom message],[trouble type],
[device type]
In the above listing 29-41 is the address of
the device in trouble, the time tells when the
device went into trouble, #7 is the number
of this trouble in the current list, [custom
message] is the custom message for the
device in trouble, [trouble type] is the type
of trouble, and [device type] is the type of
device in trouble.
(To end a menu session and return to the
Main Menu or to leave the menu at any time,
press the Up arrow key to go backward one
menu each time.)

List: Sensitivity Settings

Use List Sensitivity to show sensitivity
setting of individual smoke detectors on
analog loops.
From the List menu use the left or right
arrow key to cause the S in SENSTVTY to
start blinking:
LIST: TROUBLE SECURITY SENSTVTY
(If you press HELP at this point, the System
displays:
SHOW DETECTOR SENSITIVITIES
Note that List Sensitivity shows the sensitiv-
ity of smoke detectors only. Press HELP
again to return to the List menu.)
Display the Sensitivity Setting of One Device
Press ENTER to select List Sensitivity. The
System asks you for a module and device
number.
TYPE IN MODULE & DEVICE: 001-001
Type the three-digit module number and
three-digit device number using the nu-
meric keypad and press ENTER. (Enter all
leading zeros.)
The System displays the sensitivity setting
of the device specified (Hi_3, Hi_2, Hi_1,
Norm, Low_1, Low_2 or Low_3 ).
3-26
Press NEXT to display the address and
sensitivity setting of each succeeding
smoke detector. When the System has
shown the sensitivity settings of all smoke
detectors on that analog loop, it returns to
the List menu.
To leave the List Sensitivity menu without
going through the entire analog loop, press
the Up arrow key. The System displays the
List menu.
Print the Sensitivity Setting of All Smoke
Detectors Assigned to a Specified Module
Press PRINT when the S in SENSTVTY is
blinking. The System then asks for a
module number.
TYPE IN MODULE NUMBER: [module number]
Type the three-digit module number and
press ENTER. (Enter all leading zeros.)
The System prints the sensitivity settings
(Hi_3, Hi_2, Hi_1, Norm, Low_1, Low_2 or
Low_3, or ... if there is no smoke detector) of
all the devices assigned to the analog loop.
Sensitivities for module 1
1- HI_3
2- ... 3- NORM 4- ...
6- ...
7- ... 8- ...
11- NORM
12- ... 13- ... 14- ... 15- LOW1
NOTE: You cannot print the sensitivity
setting of a single smoke detector.
(To end a menu session and return to the
Main Menu or to leave the menu at any time,
press the Up arrow key to go backward one
menu each time.)

List: Voltages

Use List Voltages to show the voltages of
initiating devices on analog loops.
From the List menu press the Left or Right
arrow key to cause the V in VOLTAGES to
start blinking:
LIST: SECURITY, SENSTVTY, VOLTAGES
5- ...
9- ... 10- ...