Zero Clearance Framing - Regency E18-NG Manual

E18 series gas insert

Advertisement

1. When installing the E18 as a
Zero clearance, you will use
the framing clearances in the
following diagrams. Mantel
and inside corner clearances
can be found in Minimum
Clearances to Combustibles.
2. Attach the E18 to the Zero
Clearance Kit.
3. Attach the Zero Clearance Kit
to the Framing.
4. Install the Surround as per
manual.
Typical
Framing
Zero Clearance
Kit - Surround
Framing
E18 Insert

ZERO CLEARANCE FRAMING

8 3/4"
222mm
37 7/16"
951mm
Min
3 3/4"
95mm
Min
Ceiling Height
Header Height
VENTING CONFIGURATIONS
The E18 is approved to be attached to any of the approved appliances
listed in the Installation Checklist. The existing unit must be connect to
B-Vent Pipe having at least 8 feet of vertical venting and can having a
maximum of 6 feet horizontal venting with two 90 degree elbows. The
venting must terminate vertically with an approved B-Vent Cap.
When Installing the E18 as a Zero Clearance Unit, the E18 will connect to
4" B-Vent only. You must use a minimum of 8 feet of vertical pipe and you
may use up to a maximum of 6 feet of horizontal pipe with two 9 degree
elbows. The venting must terminate vertically with an approved B-Vent Cap.
All horizontal runs must maintain a 1/4" of rise for every foot of horizontal run.
E18 Gas Insert
36"
914mm
Min
15 1/2"
394mm
Min.
Chase
Depth
42 3/4"
1086mm
Min