Required Sed2 Parameter Settings - Siemens SED2 VFD Operating Instructions Manual

Electronic bypass option
Hide thumbs Also See for SED2 VFD:
Table of Contents

Advertisement

SED2 VFD Electronic Bypass Option Operating Instructions

Required SED2 Parameter Settings

The following SED2 parameters are programmed by the factory before shipping. If these
parameters are changed or if the SED2 is ever reset to factory default, you must reset these
parameters as follows:
NOTES:
1. The Interlock Start on the Controller board is simply a follower that can be used to tell the
drive to do anything by closing the SED2 Interlock Start and programming P0704.
2. The Programmable Output on the Controller board is simply a follower of the SED2 Relay.
3. The SED2 Fault must always be programmed as a fault. Do not change the SED2 relay fault
for other uses via P0731.
4. Changing P0700 resets all digital inputs and P0702 will require programming.
18
Parameter
Setting
P0748
P0702 in000
3
P0702 in001
3
P0731
52.3