B. Hearth Protection Requirements
FLOOR PROTECTION: It is necessary to install a Type I
floor protector.
In the US: The unit may be installed on a combustible floor
if the bottom heat shield is installed and non-combustible
spark & ember protection is used. The bottom heat shield
is required unless the unit will be installed on a completely
non-combustible surface (example: unpainted concrete over
bare earth). There is no required R or K value. The floor
protector should extend 8" (203 mm) from either side of the
loading door, 16" (406 mm) from the front of the unit and 6"
(152 mm) to the rear of the unit. The floor protector must
extend underneath any horizontal run of chimney connector
and extend 2" (51mm) beyond each side.
In Canada, similar floor protection must be provided 18" (457
mm) in front, 8" (203 mm) from the sides and 6" (152 mm) to
the rear of the appliance. Figure 3.8
28-1/4 in.
minimum
6 in
16 in
(FRONT DOOR OPENING)
USA
Figure 3.5
Must extend 51mm
beyond each side
of pipe (shaded area)
962mm
minimum
152MM
457MM
(FRONT DOOR OPENING)
CANADA
Figure 3.7
3-90-30007345i
44-7/8 in.
minimum
8 in
USA
Figure 3.6
1191mm
minimum
203MM
USA
Figure 3.8
Vermont Castings • Intrepid FlexBurn
*EXCEPTION: Non-combustible floor protections must
extend beneath the flue pipe when installed with horizontal
venting and extend 2" (51 mm) beyond each side. See
Figure 3.8.
Fire Risk
Hearth pads must be installed exactly as
specified. High temperatures or hot embers
may ignite concealed combustibles.
Corner hearth pad dimensions with single wall pipe
Corner hearth pad dimensions with double wall pipe
Installation Manual_R2 • 2018 - ___ • 07/18
®
!
WARNING
CANADA
CANADA
9