Set-up
Multiple Tank Setup
8
[only for 92 and 119 USG (350 and 450 L)]
Vitocell 300-H, EHA Series Installation
Two tanks, each with 92 USG (350 L) content and up
to three tanks, each with 119 USG (450 L) content,
may be stacked vertically.
1. Set-up and orient lower tank in its final location.
2. Remove levelling bolts of top tank.
3. Carefully unhook front panel.
4. Remove insulation.
5. Remove spring clip and carefully pull sensor of the
thermometer out of tank cap.
6. Pull side panels of top tank forward to remove.
1. Place top tank on top of bottom tank and align.
2. Take packaged M8 bolts, drop in holes of top tank
support brackets and fasten to bottom tank support
brackets.
3. Reinstall side panels.
IMPORTANT
Install third tank (if applicable) in an identical fashion as
the second tank.
4. Fully insert sensor into opening in tank cap and
secure using spring-clip.
5. Install insulation.
6. Install front panel.