Connections

Recirculation Connections

Connection of a recirculation system in a multiple
tank installation for systems utilizing boilers or remote
heating plants without low temperature boiler return
water and for steam heating operation with 15 psi and
one recirculation line.
Legend
A Domestic hot water
B Recirculation circuit
C Domestic cold water
Pipe domestic hot water supply piping with tank as
illustrated. Connections must be accessible for service
(use factory supplied adaptors). Connection sizes are
provided in section entitled Orientation and
Dimensions on page 9.
Install recirculation pump, flow-check valve and
recirculation timer (for shut-down during off-hours
where feasible) on the recirculation piping side.
Gravity circulation of the recirculation system is
restricted due to the upward-curved domestic hot
water discharge piping inside the tank.
Connect tank battery to existing recirculation piping.
Cap off unused recirculation connections of
individual tanks.
Saving Energy
A timer on the recirculation pump reduces the heat loss
significantly in commercial applications during times when
no or reduced demand for domestic hot water occurs.
18
Vitocell 300-H, EHA Series Installation
Connection of a recirculation system in a multiple
tank installation for remote heating plants with low
temperature boiler return water limit and/or for multiple
recirculation lines.
Legend
A Domestic hot water
B Recirculation circuit
C Domestic cold water
Recirculation tapping
[only for 92 and 119 USG (350 and 450 L)]
Legend
A 42 and 53 USG (160 and 200 L) storage capacity
B 92 and 119 USG (350 and 450 L) storage capacity
The recirculation tapping on the tank is also the opening
for mounting the temperature and pressure relief valve
(T&P valve).
If this opening is utilized for recirculation, extend the
stainless steel nipple on the tank with a brass tee
(field supplied) of the same size as the stainless steel
nipple diameter to accommodate both connections.