Appliance Location; Framing Dimensions; Clearances To Combustibles; Hearth Extensions - Heatilator Icon I100 Dimension Manual

50" wood fireplace
Hide thumbs Also See for Icon I100:

Advertisement

Specifications

APPLIANCE LOCATION

74-1/4"
24-3/8"
[1886]
[619]
61-5/8"
Across a
[1565]
corner
52-1/2"
104-7/8"
[1334]
[2664]
As a
room
77-5/8"
divider
[1972]
48"
[1219]
24"
[610]
MANTEL PROJECTIONS
Combustible Wall
2 x 4 stud wall
Front Standoffs
Non-combustible
Decorative Facing
such as: steel, iron
brick, tile, concrete,
slate, plasters
1-1/ 2" [38]
maximum
Measured from top of fireplace opening
Seal joint with
Grid represents 1" squares
non-combustible
sealant
MANTEL LEG/WALL PROJECTIONS
Grid represents
1" scale
FLUSH
FRONT
22-3/8"
[568]
60-5/8" [1540]
24"
[610]

HEARTH ExTENSIONS

12"
[305]
50"
[1270]
74"
[1880]
30-1/2"
[775]
77-5/8" [1972]
24"
[610]
In an exterior chase
or projecting into
a garage
30-1/2"
[775]
1/2" [13] all
Along a wall
configurations
77-5/8" [1972]
30-1/2"
[775]
7 ft [2134] minimum
Combustible
base of fireplace
Decorative Facing
to ceiling
12" [305]
Mantel
20" [508]
minimum
12" [305]
minimum
6" [152]
minimum
BRICK
[102]
FRONT
50" [1270]
19-3/4"
[502]
24"
[610]
12"
[305]
Raised Hearth
Flush Hearth
20" [508]
30" [762]
minimum
minimum
Lakeville, MN
Web: www.heatilator.com

FRAMING DIMENSIONS

2" [51]
Header will sit
on top of front
standoffs after
fireplace is
installed.
**30-1/2"
[722]
** If interior of chase will be
drywalled, add the thickness
to this measurement

CLEARANCES TO COMBuSTIBLES

Storm Collar
Roof Flashing
Ceiling Firestop
2" [51]
minimum
0" to level
of standoffs
4"
0" from
floor
HEARTH ExTENSION CONSTRuCTION
1/2" [13] Micore or
equivalent insulation
See Install Manual
Floor constructed of wood or
other combustible material
PRODUCT LISTING CODES
US
UL 127
Additional information can be found online at www.heatilator.com
Phone: (800) 927-6841
1/2"
[13]
17"
[432]
Fireplace must be set out
1/2 [13] in front of the face
of the framing material.
Use only non-combustible
material below the top of
the front standoffs.
61-5/8"
*8"
[1565]
[203]
* Extra space needed (both sides)
for outside air connection. If outside
air duct has no bend, this dimension
may be reduced as long as minimum
clearances are met.
2" [51]
minimum
2" [51]
Attic
minimum
Insulation
Shield
(attic)
Ceiling Firestop
(ceiling)
2" [51]
2" [51]
minimum
minimum
Offset/Return with
hanger straps
(ceiling)
2" [51]
minimum 2" [51] minimum
to header
1-1/2" [38] from
back of unit
1-1/2" [38] from side of unit
(except at nailing flanges
where it is 1/2" [13]
Continuous, non-combustible
sealant
Tile, stone or other
non-combustible material
2" [51]
required
Product information provided is not
complete and is subject to change without
notice. Product installation must adhere
strictly to instructions accompanying
product to avoid risk of fire and potential
injury.