Error
Code
Error Contents and Cause
(SD0)
The instruction cannot process the
4100
contained data.
• The number of setting data dealt with
the instruction exceeds the applicable
range.
• The storage data and constant of the
device specified by the instruction
exceeds the applicable range.
• When writing to the host CPU shared
memory, the write prohibited area is
specified for the write destination
4101
address.
• The range of storage data of the
device specified by the instruction is
duplicated.
• The device specified by the
instruction exceeds the range of the
number of device points.
• The interrupt pointer No. specified by
the instruction exceeds the applicable
range.
• The network No. or station No.
specified for the dedicated instruction
is wrong.
• The link direct device (J \ ) setting
4102
is incorrect.
• The module No./ network No./number
of character strings exceeds the
range that can be specified.
The configuration of the PID dedicated
4103
instruction is incorrect.
The number of settings is beyond the
4104
range.
Numbers of execution to the CC-Link
4107
instruction are beyond 32.
The CC-Link parameter is not set when
4108
the CC-Link instruction is executed.
Corrective Action
Read the common information of the
error using the peripheral device, check
error step corresponding to its
numerical value (program error
location), and correct the problem.
Read the common information of the
error using the peripheral device, check
error step corresponding to its
numerical value (program error
location), and correct the problem.
Read the common information of the
error using the peripheral device, check
error step corresponding to its
numerical value (program error
location), and correct the problem.
Read the common information of the
error using peripheral device, and check
and correct the program corresponding
to that value (program error location).
Set the numbers of execution to the
CC-Link instruction to 32 or less.
Execute the CC-Link instruction after
setting the CC-Link parameter.
102
Corresponding
CPU
QnA
QnA
QnA
QnA
Q4AR
QnA
QnA