Operation Overview - Johnson Controls P352PN-2 Product Manual

System 350tm p352pn series electronic proportional plus integral pressure controls for psi applications
Table of Contents

Advertisement

A
pplication
A P352PN Series pressure control may be set as a
proportional-only control or as a proportional plus
integral control, to generate two standard analog
output signals (0 to 10 VDC and 4 to 20 mA).
The P352PN controls can be used as stand-alone
devices or in conjunction with plug-together power,
stage, and display modules.
A typical System 350 pressure control application
includes the following:
P352PN Pressure Control
Y350R Power Module (or 24 VAC transformer)
S352AA-2 Stage Module
D352AA-2 Digital Pressure Display Module
P399 Pressure Transducer
Typical P352PN pressure control applications include:
Condenser fan speed control
Damper positioning
Flow valve positioning
Setpoint Potentiometer
Minimum Output
Potentiometer
Throttling Range
Potentiometer
Integration
DIP Switch
0 to 10 VDC Output
0 to 20 mA Output
Common for Analog
Outputs
2
Basic Controls—P352PN Electronic Proportional Plus Integral Pressure Controls for PSI Applications
PSI
THROT
MIN
RANGE
OUTPUT
Figure 2: Interior View and Typical Wiring of P352PN Control
O
peration Overview
IMPORTANT: The P352PN controls are intended to
The P352PN control operates on 24 VAC and provides
two analog output signals: 0 to 10 VDC and 0 to
20 mA. A 10-segment front panel LED bar graph
indicates percentage of output. Adjustable features
include:
Setpoint
Minimum output
Throttling range (proportional band)
Integration constant
Reverse acting or direct acting mode of operation
Module Connector
J1 Jumper
Positions
Reverse Acting
Direct Acting
LED Indicator
(Percent of Output)
24 VAC Transformer
(If a Y350R Power Module
is not used)
24 VAC
Connect Cable
Shield to C
Black wire to C
Red wire to VDC
control equipment under normal
operating conditions. Where failure or
malfunction of the P352PN control
could lead to an abnormal operating
condition that could cause personal
injury or damage to the equipment or
other property, other devices (limit or
safety controls) or systems (alarm or
supervisory systems) intended to warn
of, or protect against, failure or
malfunction of the P352PN control
must be incorporated into and
maintained as part of the control
system.
P399
Transducer
WHA-P399
Wiring Harness
120/240 VAC
White wire to SN