Automatic water control valve preaction type a systems (en12845 compliance) dn40 to dn200
Hide thumbs Also See for tyco DV-5A:
Table of Contents

Advertisement

TFP1485
Page 6 of 20
SYSTEM PIPING WITH AUTOMATIC SPRINKLERS - NORMALLY DRY
MANUAL ELECTRIC
PULL STATION
(AS REQUIRED)
DELUGE VALVE
RELEASING PANEL
(AUTOMATIC
CONTROL UNIT
WITH BATTERY
BACK-UP)
POWER
AUTOMATIC
SUPPLY
AIR/NITROGEN
(TYPICALLY
120 VOLTS AC)
(GRAPH A)
SUPERVISORY
LOW PRESSURE
ALARM SWITCH
DIAPHRAGM
CHAMBER SUPPLY
SYSTEM AIR
PRESSURE
CONTROL VALVE
(NORMALLY OPEN)
GAUGE

Operation

The TYCO DV-5
Valve is a diaphragm
a
style valve that depends upon water
pressure in the Diaphragm Chamber
(Ref. Figure 2A) to hold the Diaphragm
closed against the water supply
pressure.
When the DV-5
Valve is set for service,
a
the Diaphragm Chamber is pressurized
through the trim connections from the
inlet side of the system's main control
valve.
Opening an actuation device (solenoid
valve or dry pilot actuator) trips the
Model MRA-1 Manual Reset Actuator.
Tripping the MRA-1 releases water from
the DV-5
Diaphragm Chamber faster
a
than it can be replenished through the
1/8 in. (3,2 mm) restriction located in
the diaphragm chamber supply con-
nection. Release of water through the
MRA-1 results in a rapid pressure drop
in the DV-5
Diaphragm Chamber. The
a
force differential applied through the
Diaphragm to hold the Diaphragm in
the set position is reduced below the
valve trip point. The water supply pres-
sure then forces the Diaphragm open
permitting water to flow into the system
piping, as well as through the Alarm
ELECTRIC DETECTION SYSTEM
(TYPICALLY 24 VOLTS DC)
HEAT DETECTORS, SMOKE DETECTORS,
MANUAL PULL STATIONS, ETC.
N.O.
N.O.
DIAPHRAGM CHAMBER
SUPPLY
PRESSURE GAUGE
RESTRICTION
MANUAL RESET
WATER SUPPLY SHUT-OFF
(NORMALLY OPEN)
DV-5
VALVE - PREACTION TYPE A SYSTEM
a
SCHEMATIC DIAGRAM
Port to actuate the system alarms (Ref.
Figure 2B).
In normal operation, the system air
pressure is monitored by a Super-
visory Low Pressure Alarm Switch.
Should damage occur to a sprinkler or
the system piping, loss of air pressure
will not result in opening of the DV-5
Valve and flooding of the system with
resulting inadvertent water discharge.
Loss of system air pressure will only
result in a low air alarm so that repairs
to the system can be facilitated to avoid
unnecessary water damage should the
system be activated in the event of a
fire.
However, in the event of a fire, opera-
tion of an electrical detection device
such as a heat-sensitive thermostat
or smoke detector signals the deluge
valve releasing panel to energize the
normally closed Solenoid Valve. In
turn, the energized Solenoid Valve
opens to release water from the Dia-
phragm Chamber faster than it can be
replenished through the restriction pro-
vided in the diaphragm supply connec-
tion. This release of water results in a
rapid pressure drop in the Diaphragm
Chamber to below the valve trip point.
The water supply pressure then forces
the Diaphragm open, permitting water
WATERFLOW
DV-5A
PRESSURE
VALVE
ALARM
SWITCH
DRAIN
WATER SUPPLY
PRESSURE
ACTUATOR
GAUGE
DIAPHRAGM CHAMBER
SUPPLY CONNECTION
FIGURE 4
SOLENOID
VALVE
(NORMALLY
CLOSED
ENGERGIZED)
SYSTEM DRAIN VALVE
DRAIN
(NORMALLY CLOSED)
DRAIN
DRAIN
CONTROL
MAIN
CONTROL VALVE
(NORMALLY
WATER
OPEN)
SUPPLY
to flow into the system piping, as well
as through the Alarm Port to actuate
the system alarms.
In the event of a fault detection in the
fire detection system, the system con-
verts to operate as an ordinary dry pipe
system, which means the energized-to-
close Solenoid Valve in the actuation
a
loop becomes de-energized and open
to communicate any system air pres-
sure loss to the DP-1 Dry Pilot Actu-
ator. As soon as a sprinkler operates/
activates, the subsequent drop in air
pressure opens the Dry Pilot Actuator.
Water from the diaphragm pressure
piping will exit the Dry Pilot Actuator
through this drain, resulting in the acti-
vation of the DV-5
Deluge Valve.
a
Upon opening of the DV-5
whether by Solenoid Valve or Dry Pilot
Actuator, the Model MRA-1 Manual
Reset Actuator (Ref. TFP1387) opens
to constantly vent the DV-5
phragm Chamber to hydraulically latch
the DV-5
in the tripped position until
a
manually reset.
SOLENOID
VALVE
(NORMALLY
CLOSED
DE-ENGERGIZED)
DRY PILOT
ACTUATOR
DRAIN
MAIN
DRAIN VALVE
(NORMALLY
CLOSED)
LOCAL
MANUAL
DRAIN
STATION
Valve,
a
Dia-
a