200
400
9.0
8.0
7.0
6.0
5.0
4.0
3.0
2.0
1.0
0.9
0.8
0.7
0.6
0.5
0.4
0.3
50
100
5 ± 1 psi (0,34 ± 0,07 bar) on decreas-
ing pressure. The Pressure Relief Valve
(Item S- Figs. 16, 17, 18) is factory set to
fully open at 25 ± 2 psi (1,72 ± 0,14 bar)
and it begins to crack open at a pres-
sure of about 18 psi (1,24 bar).
Materials of
Construction
Body
Epoxy coated ductile iron per ASTM
A536-77, Grade 65-45-12
Handhole Cover
Epoxy coated ductile iron per ASTM
A536-77, Grade 65-45-12
Diaphragm
Polyester fabric reinforced, TEFLON
coated, EPDM rubber per ASTM D2000
Diaphragm Cover Fasteners
Aluminum zinc coated steel
FLOW RATE IN LITERS PER MINUTE (LPM)
(1 GPM = 3,785 LPM)
600
1000
200
400
FLOW RATE IN GALLONS PER MINUTE (GPM)
GRAPH A
DV-5
NOMINAL PRESSURE LOSS VERSUS FLOW
Common Hardware Trim
• Common hardware pipe fittings are
galvanized or black as required and
are malleable per ASME B16.3.
• Common hardware pipe nipples are
galvanized or black as required and
are Schedule 40 per ASTM A53 or
A135.
• Common hardware compression
fittings are brass per ASTM B16.
• Common hardware tubing is Type L
copper per ASTM B88.

Operation

The TYCO DV-5
a
style valve that depends upon water
pressure in the Diaphragm Chamber
(Ref. Figure 2A) to hold the Diaphragm
closed against the water supply
pressure.
When the DV-5
Valve is set for service,
a
the Diaphragm Chamber is pressurized
through the trim connections from the
2000
3000
5000
600
1000
VALVE
a
inlet side of the system's main control
valve.
Opening an actuation device, for
example the solenoid valve in the Elec-
tric Actuation Trim (Ref. Figure 6), trips
the Model MRA-1 Manual Reset Actua-
tor. Tripping the MRA-1 releases water
from the DV-5
faster than it can be replenished
through a 1/8 in. (3,2 mm) restriction
located in the Diaphragm Chamber
Supply Connection. Release of water
through the MRA-1 results in a rapid
pressure drop in the DV-5
Chamber. The force differential applied
through the Diaphragm to hold the
Diaphragm in the set position is then
Valve is a diaphragm
reduced below the valve trip point. The
water supply pressure then forces the
Diaphragm open permitting water to
flow into the system piping, as well as
through the Alarm Port to actuate the
system alarms (Ref. Figure 2B).
Upon opening of the DV-5
Model MRA-1 Manual Reset Actuator
TFP1425
Page 5 of 34
7000
10000
15000
0,600
0,500
0,400
0,300
0,200
0,100
0,090
0,080
0,070
0,060
0,050
0,040
0,030
0,022
2000
3000
4000
Diaphragm Chamber
a
Diaphragm
a
Valve, the
a

Advertisement