Specifications - Johnson Controls P352PN-2 Product Manual

System 350tm p352pn series electronic proportional plus integral pressure controls for psi applications
Table of Contents

Advertisement

S
pecifications
Product
Setpoint and
Throttling Ranges
Supply Power
Requirements
Add-on Modules:
Y350R Power Module
D352 Display Module
S352AA-2 Stage Module
Analog Output
Minimum Output Signal
Magnitude
Output Indication
Control Action
Integration Constant
Ambient Temperature
Ambient Humidity
(all modules)
Material
Agency Listings
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult Johnson Controls/PENN Application Engineering at (414) 274-5535. Johnson Controls, Inc. shall not be liable for
damages resulting from misapplication or misuse of its products.
Controls Group
507 E. Michigan Street
P.O. Box 423
Milwaukee, WI 53201
12
Basic Controls—P352PN Electronic Proportional Plus Integral Pressure Controls for PSI Applications
P352PN Electronic, Proportional Plus Integral Pressure Controls for PSI Applications
P352PN-2: Setpoint Range 0-100 psi; Throttling Range 5-50 psi
P352PN-3: Setpoint Range 90-250 psi; Throttling Range 10 to 100 psi
P352PN-4: Setpoint Range 240-600 psi; Throttling Range 10 to 100 psi
AC Supply: 24 VAC Class 2, 50/60 Hz, (20 to 30 VAC) 5 VA (for P352PN control only)
Y350R Power Module: See Add-on Modules below.
Input Voltage: 120/240 VAC, 50/60 Hz
Display Range of 0 to 750 psi
SPDT Enclosed Output Relay rated for 10 A Non-inductive, 125 VA Pilot Duty-24/240 VAC,
1/2hp 120/240 VAC
0 to 10 VDC (550 ohm Load Minimum) and 0 to 20 mA (600 ohm Load Maximum)
Adjustable from 0 to 60% of Full Output Signal Range
A 10-segment LED bar graph indicates percentage of output.
Direct or reverse action is jumper selectable.
Three Selectable Integration Constants: Slow, Medium, Fast, and an OFF (or Proportional
Only Control) Position
Operating:
-30 to 150°F (-34 to 66°C)
Shipping:
-40 to 185°F (-40 to 85°C)
0 to 95% RH Non-condensing; Maximum Dew Point: 85°F (29°C)
Case, Cover: NEMA 1 High-impact Thermoplastic
UL Listed, CCN XAPX, File E27734
UL Listed for Canada, CCN XAPX7, File E27734