4-4. STANDARD OPERATION DATA
PUHZ-SP100YKA.TH
PUHZ-SP125VKA.TH
PUHZ-SP140VKA.TH
Representative matching
Mode
Total
Capacity
input
Electrical
Indoor
circuit
Phase, Hz
Voltage
Current
Outdoor
Phase, Hz
Voltage
Current
Refrigerant
Discharge Pressure
circuit
Suction pressure
Discharge temperature :
Condensing temperature :
Suction temperature
Ref. pipe length
Indoor
Intake air
side
temperature
Discharge air
temperature
Outdoor
Intake air
side
temperature
SHF
BF
The unit of pressure has been changed to MPa based on international SI system.
The conversion factor is : 1(MPa)=10.2(kgf/cm²)
OCH671
PUHZ-SP125YKA.TH
PUHZ-SP140YKA.TH
PUHZ-SP100
COOLING
W
9.4
kW
3.29
PLA-SM100EA.UK
1, 50
V
230
A
0.46
PUHZ-SP100YKA
1, 50
V
230
A
14.0/5.0
MPa
2.79
MPa
0.86
77.9
47.0
12.6
:
m
7.5
DB
27
:
WB :
19
DB
13.5
:
DB
35
:
WB :
24
0.77
0.24
PUHZ-SP125
HEATING
COOLING
11.2
12.1
3.48
4.23
PLA-SM125EA.UK
1, 50
230
0.44
0.66
PUHZ-SP125VKA
PUHZ-SP125YKA
3, 50
1, 50
400
230
14.0/5.0
18.0/6.5
2.68
3.00
0.68
0.85
78.5
76.7
45.3
49.9
3.0
7.5
7.5
20
27
14
19
39.9
12.2
7
35
6
24
0.73
0.15
9
PUHZ-SP140
HEATING
COOLING
13.5
13.6
4.18
5.63
PLA-SM140EA.UK
1, 50
230
0.64
0.66
PUHZ-SP140VKA
PUHZ-SP140YKA
3, 50
1, 50
400
230
17.5/6.5
23.5/9.0
2.62
3.21
0.65
0.77
69.7
88.1
44.6
53.2
−0.8
7.9
7.5
20
27
14
19
42.1
11.3
7
35
6
24
0.70
0.14
HEATING
15.0
4.81
0.64
3, 50
400
20.5/7.5
2.78
0.62
72.6
47.0
−2.0
20
14
44.3
7
6