Och671 - Mitsubishi Electric PUHZ-SP125VKA Service Manual

R410a, outdoor unit
Hide thumbs Also See for PUHZ-SP125VKA:
Table of Contents

Advertisement

Type of
Switch
No.
Switch
1
SW5
2
3,4,5,6
1
2
SW7
*4
3
4
5
6
1
SW8
2
3
1
SW9
2
3,4
Dip
switch
1
2
3
4
SW6
5
6
7
8
*
2
'Power failure automatic recovery' can be set by either remote controller or this DIP SW. If one of them is set to ON, 'Auto
recovery' activates. Please set "Auto recovery" basically by remote controller because not all units have DIP SW.
Please refer to the indoor unit installation manual.
*
3
SW7-1,2 are used for demand control. SW7-1,2 are effective only at the demand control.
(Refer to the next page : Special function (b))
*
4
Please do not use SW7-3 to 7-5 usually. Trouble might be caused by the usage condition.
*
5
SW6-1 to 3: Function switch.

OCH671

Function
No function
Power failure
automatic recovery
*2
No function
Setting of demand
control
*3
Max Hz setting (cooling)
Max Hz (cooling) o 0.8
Max Hz setting (heating) Max Hz (heating) o 0.8
No function
Defrost Hz setting
No function
No function
No function
No function
Function switch
No function
No function
No function
Fan motor check mode
Action by the switch operation
ON
Auto recovery
No auto recovery
SW7-1
SW7-2
OFF
OFF
ON
OFF
OFF
ON
For high humidity
Valid
ON
*5
MODEL
SW6-4, 5, 6, 7, 8
ON
125V
OFF
1 2 3 4 5 6 7 8
ON
140V
OFF
1 2 3 4 5 6 7 8
ON
100Y
OFF
1 2 3 4 5 6 7 8
ON
125Y
OFF
1 2 3 4 5 6 7 8
ON
140Y
OFF
1 2 3 4 5 6 7 8
65
Effective timing
OFF
When power supply ON
Power consumption
(Demand switch ON)
0% (Operation stop)
50%
75%
Normal
Always
Normal
Always
Normal
Always
Normal
Always
When power supply ON
OFF
during test run