Mitsubishi Electric PUHZ-SP125VKA Service Manual

Mitsubishi Electric PUHZ-SP125VKA Service Manual

R410a, outdoor unit
Hide thumbs Also See for PUHZ-SP125VKA:

Advertisement

SPLIT-TYPE AIR CONDITIONERS

SERVICE MANUAL

Outdoor unit

[Model Name]

PUHZ-SP125VKA
PUHZ-SP140VKA
PUHZ-SP100YKA
PUHZ-SP125YKA
PUHZ-SP140YKA
R410A
[Service Ref.]
PUHZ-SP125VKA.TH
PUHZ-SP140VKA.TH
PUHZ-SP100YKA.TH
PUHZ-SP125YKA.TH
PUHZ-SP140YKA.TH
CONTENTS
1. REFERENCE MANUAL ···························· 2
2. SAFETY PRECAUTION ···························· 2
3. SPECIFICATIONS ··································· 6
4. DATA ···················································· 7
5. OUTLINES AND DIMENSIONS ················ 10
6. WIRING DIAGRAM ································ 11
7. WIRING SPECIFICATIONS ····················· 13
8. REFRIGERANT SYSTEM DIAGRAM ·········· 18
9. TROUBLESHOOTING ···························· 20
10. FUNCTION SETTING ····························· 77
12. EASY MAINTENANCE FUNCTION ··········· 99
13. DISASSEMBLY PROCEDURE ················103
PARTS CATALOG (OCB671)
September 2017
No.OCH671

Advertisement

Table of Contents
loading

Summary of Contents for Mitsubishi Electric PUHZ-SP125VKA

  • Page 1: Table Of Contents

    SPLIT-TYPE AIR CONDITIONERS September 2017 No.OCH671 SERVICE MANUAL R410A Outdoor unit [Model Name] [Service Ref.] PUHZ-SP125VKA.TH PUHZ-SP125VKA PUHZ-SP140VKA.TH PUHZ-SP140VKA PUHZ-SP100YKA.TH PUHZ-SP100YKA PUHZ-SP125YKA.TH PUHZ-SP125YKA PUHZ-SP140YKA.TH PUHZ-SP140YKA CONTENTS 1. REFERENCE MANUAL ···························· 2 2. SAFETY PRECAUTION ···························· 2 3. SPECIFICATIONS ··································· 6 4.
  • Page 2: Reference Manual

    REFERENCE MANUAL INDOOR UNIT SERVICE MANUAL Service Model name Service Ref. Manual No. OCH683 PLA-SM71/100/125/140EA* PLA-SM71/100/125/140EA.UK OCB683 PEAD-SM71/100/125/140JA(L) PEAD-SM71/100/125/140JA(L).UK — * These models will be released on Dec/2017. SAFETY PRECAUTION 2-1. ALWAYS OBSERVE FOR SAFETY Before obtaining access to terminal, all supply circuits must be disconnected. 2-2.
  • Page 3 Use a vacuum pump with a reverse flow check Use new refrigerant pipes. valve. In case of using the existing pipes for R22, be careful with Vacuum pump oil may flow back into refrigerant cycle and the following. that can cause deterioration of refrigerant oil, etc. •...
  • Page 4 [3] Service tools Use the below service tools as exclusive tools for R410A refrigerant. Tool name Specifications Gauge manifold • Only for R410A • Use the existing fitting specifications . (UNF1/2) • Use high-tension side pressure of 5.3MPa·G or over. Charge hose •...
  • Page 5 (2) Cautions for refrigerant piping work New refrigerant R410A is adopted for replacement inverter series. Although the refrigerant piping work for R410A is same as for R22, exclusive tools are necessary so as not to mix with different kind of refrigerant. Furthermore as the working pressure of R410A is 1.6 times higher than that of R22, their sizes of flared sections and flare nuts are different.
  • Page 6: Specifications

    SPECIFICATIONS Service Ref Power supply Single phase, 50 Hz, 230 V 3-phase, 50 Hz, 400 V (phase,cycle,voltage) Max. current 26.5 11.5 11.5 11.5 External finish Munsell 3Y 7.8/1.1 Refrigerant control Linear Expansion Valve Compressor Hermetic Model MNB33FBDMC-L MNB33FBDMC-L SNB220GBAMT MNB33FBDMC-L MNB33FBDMC-L Motor output Starter type Direct input...
  • Page 7: Data

    DATA 4-1. REFILLING REFRIGERANT CHARGE (R410A : kg) Piping length (one way) Initial Service Ref. charged PUHZ-SP125VKA.TH PUHZ-SP140VKA.TH PUHZ-SP100YKA.TH PUHZ-SP125YKA.TH PUHZ-SP140YKA.TH 4-2. COMPRESSOR TECHNICAL DATA (at 20°C) PUHZ-SP125/140VKA.TH Service Ref. PUHZ-SP100YKA.TH PUHZ-SP125/140YKA.TH Compressor model SNB220FBAMT MNB33FBDMC-L 0.95 0.88 Winding 0.95 0.88...
  • Page 8 4-3. NOISE CRITERION CURVES PUHZ-SP100YKA.TH PUHZ-SP125VKA.TH SPL(dB) SPL(dB) MODE LINE MODE LINE PUHZ-SP125YKA.TH COOLING COOLING HEATING HEATING NC-70 NC-70 NC-60 NC-60 NC-50 NC-50 NC-40 NC-40 NC-30 NC-30 APPROXIMATE APPROXIMATE THRESHOLD OF THRESHOLD OF HEARING FOR NC-20 HEARING FOR NC-20 CONTINUOUS...
  • Page 9 4-4. STANDARD OPERATION DATA PUHZ-SP100YKA.TH PUHZ-SP125VKA.TH PUHZ-SP125YKA.TH PUHZ-SP140VKA.TH PUHZ-SP140YKA.TH Representative matching PUHZ-SP100 PUHZ-SP125 PUHZ-SP140 Mode COOLING HEATING COOLING HEATING COOLING HEATING Total Capacity 11.2 12.1 13.5 13.6 15.0 input 3.29 3.48 4.23 4.18 5.63 4.81 Electrical Indoor PLA-SM100EA.UK PLA-SM125EA.UK PLA-SM140EA.UK...
  • Page 10: Outlines And Dimensions

    OUTLINES AND DIMENSIONS PUHZ-SP100YKA.TH PUHZ-SP125VKA.TH PUHZ-SP125YKA.TH PUHZ-SP140VKA.TH PUHZ-SP140YKA.TH Unit: mm OCH671...
  • Page 11: Wiring Diagram

    WIRING DIAGRAM PUHZ-SP125VKA.TH PUHZ-SP140VKA.TH SYMBOL NAME SYMBOL NAME SYMBOL NAME Terminal Block <Power Supply, Indoor/Outdoor> 21S4 Solenoid Valve (4-Way Valve) Switch <Model Select> Motor for Compressor DCL1, DCL2, DCL3 Reactor Switch <Function Switch> Fan Motor CY1, CY2 Capacitor Switch <Function Switch>...
  • Page 12 PUHZ-SP100YKA.TH PUHZ-SP125YKA.TH PUHZ-SP140YKA.TH SYMBOL NAME SYMBOL NAME SYMBOL NAME Terminal Block <Power Supply> 21S4 Solenoid Valve (4-Way Valve) Switch <Function Switch> Terminal Block <Indoor/Outdoor> ACL4 Reactor Switch <Model Select> Motor for Compressor Reactor Switch <Function Switch> Fan Motor Resistor Switch <Function Switch> High Pressure Switch CY1, CY2 Capacitor...
  • Page 13: Wiring Specifications

    WIRING SPECIFICATIONS 7-1. FIELD ELECTRICAL WIRING (power wiring specifications) Outdoor unit model PUHZ-SP125VKA PUHZ-SP140VKA PUHZ-SP100/125/140YKA Outdoor unit power supply ~/N (single), 50 Hz, 230 V ~/N (single), 50 Hz, 230 V 3N~ (3 ph 4-wires), 50 Hz, 400 V Outdoor unit input capacity Main switch (Breaker)
  • Page 14 7-2. SEPARATE INDOOR UNIT/ OUTDOOR UNIT POWER SUPPLIES The following connection patterns are available. The outdoor unit power supply patterns vary on models. 1:1 System The optional indoor power supply terminal kit is required. A Outdoor unit power supply B Earth leakage breaker C Wiring circuit breaker or isolating switch D Outdoor unit E Indoor unit/outdoor unit connecting cords...
  • Page 15 7-3. INDOOR – OUTDOOR CONNECTING CABLE The cable shall not be lighter than design 60245 IEC or 60227 IEC. Wire No. o Size (mm²) Outdoor power supply Max. 45m Max. 50m Indoor unit-Outdoor unit 3 o 1.5 (polar) 3 o 2.5 (polar) Indoor unit-Outdoor unit earth 1 o Min.
  • Page 16 7-4. M-NET WIRING METHOD (Points to note) (1) Outside the unit, transmission wires should stay away from electric wires in order to prevent electromagnetic noise from making an influence on the signal communication. Place them at intervals of more than 5 cm. Do not put them in the same conduit tube.
  • Page 17 M-NET wiring (1) Use 2-core × 1.25mm² shield wire for electric wires. M-NET terminal (Excluding the case connecting to system controller.) Earth block wire (2) Connect the wire to the M-NET terminal block. Connect one core of the transmission wire (non-polar) to A terminal and the other to B. Peel the shield wire, twist the shield part to a string and connect it to S terminal.
  • Page 18: Refrigerant System Diagram

    REFRIGERANT SYSTEM DIAGRAM PUHZ-SP100YKA.TH PUHZ-SP125VKA.TH PUHZ-SP125YKA.TH PUHZ-SP140VKA.TH PUHZ-SP140YKA.TH Unit : mm (inch) Thermistor TH7 (Ambient) Heat exchanger Thermistor TH6 (Condenser) Stop valve 4-way valve Strainer Refrigerant GAS pipe connection [15.88 (5/8) Charge plug Distributor Muffler Charge plug High pressure switch 63H...
  • Page 19 8-1. REFRIGERANT COLLECTING (PUMP DOWN) When relocating or disposing of the indoor/outdoor unit, pump down the system following the procedure below so that no refriger- ant is released into the atmosphere. 1 Turn off the power supply (circuit breaker). 2 Connect the low pressure valve on the gauge manifold to the charge plug (low pressure side) on the outdoor unit. 3 Close the liquid stop valve completely.
  • Page 20: Troubleshooting

    TROUBLESHOOTING 9-1. TROUBLESHOOTING <Check code display by self-diagnosis and actions to be taken for service (summary)> Present and past check codes are logged, and they can be displayed on the wired remote controller and control board of out- door unit. Actions to be taken for service, which depends on whether or not the trouble is reoccurring in the field, are summa- rized in the table below.
  • Page 21 9-2-2. Test run for wired remote controller <PAR-3xMAA("x" represents 0 or later)> MENU RETURN SELECT ON/OFF Function buttons Select "Service" from the Main menu, and press the button. Test run Input maintenance info. Function setting Check Self check Select "Test run" with the F1 or F2 button, and press the button.
  • Page 22: Error Information

    <Error information> When an error occurs, the following screen will appear. Check the error status, stop the operation, and consult your dealer. Check code, error unit, refrigerant address, unit model name, and serial Error information number will appear. Error code The model name and serial number will appear only if the information have Error unit Ref.
  • Page 23 <Checking the error information> While no errors are occurring, page 2/2 of the error information can be viewed by Main Main menu selecting "Error information" from the Main menu. Restriction Energy saving Errors cannot be reset from this screen. Night setback Filter information Error information Main display:...
  • Page 24 9-2-3. Test run for wired remote controller <PAR-21MAA> Operating procedures While the room temperature display on the remote "TEST RUN" and the currently selected controller is “PLEASE WAIT”, the remote controller is disabled. operation mode are displayed alternately. Wait until “PLEASE WAIT” disappears before using remote controller. 1.
  • Page 25 9-2-4. Test run for wireless remote controller Measure an impedance between the power supply terminal block on the outdoor unit and ground with a 500 V Megger and check that it is equal to or greater than 1.0M". 1 Turn on the main power to the unit. TEST RUN 2 Press the button twice continuously.
  • Page 26 9-3. HOW TO PROCEED "SELF-DIAGNOSIS" 9-3-1. Self-diagnosis <PAR-31MAA> Select "Service" from the Main menu, and press the button. Test run Input maintenance info. Function setting Check Select "Self check" with the F1 or F2 button, and press the button. Self check With the F1 or F2 button, enter the refrigerant address, and press the button.
  • Page 27 9-3-2. Remote controller check <PAR-31MAA> If operations cannot be completed with the remote controller, diagnose the remote controller with this function. Select "Service" from the Main menu, and press the button. Maintenance password Remote controller check Select "Remote controller check" with the F1 or F2 button, and press button.
  • Page 28 9-3-3. Self-diagnosis <PAR-21MAA> When a problem occurs to the air conditioner, the indoor and outdoor units will stop, and the problem is shown in the remote controller display. [CHECK] and the refrigerant address are displayed on the temperature display, and the check code and unit number are displayed alternately as shown below.
  • Page 29: Remote Controller Diagnosis

    When the error history is reset, the display will look like the one shown below. Press the ON/OFF button ( in the picture in the previous page) twice However, if you fail to reset the error history, the error content will be displayed again. within 3 seconds.
  • Page 30 9-3-6. Self-diagnosis <Wireless remote controller> <In case of trouble during operation> When a malfunction occurs to air conditioner, both indoor unit and outdoor unit will stop and operation lamp blinks to inform unusual stop. < Malfunction-diagnosis method at maintenance service> [Procedure] 1.
  • Page 31: Heating

    • Refer to the following tables for details on the check codes. [Output pattern A] Beeper sounds Beep Beep Beep Beep Beep Beep Beep OPERATION · · · Repeated INDICATOR lamp flash pattern Approx. 2.5 s 0.5 s 0.5 s 0.5 s Approx.
  • Page 32: Wiring Diagram

    9-4. SELF-DIAGNOSIS ACTION TABLE <Abnormalities detected when the power is ON> Abnormal points and detection method Judgment and action Check code Case 1 No voltage is supplied to termi- 1 Check following items. nal block (TB1) of outdoor unit. a) Power supply breaker is a) Power supply breaker turned off.
  • Page 33 Abnormal points and detection method Case Judgment and action Check code 1 Check disconnection or looseness or polarity Miswiring of indoor/outdoor unit 1 Contact failure or miswiring of indoor/outdoor unit connecting of indoor/outdoor unit connecting wire of connecting wire wire indoor and outdoor units.
  • Page 34 <Abnormalities detected while unit is operating> Abnormal points and detection method Judgment and action Check code Case High pressure (High pressure switch 1 Short cycle of indoor unit 1–6 Check indoor unit and repair defect. 63H operated) 2 Clogged filter of indoor unit 3 Decreased airflow caused by Abnormal if high pressure switch 63H dirt of indoor fan...
  • Page 35 Abnormal points and detection method Judgment and action Check code Case 1 Check connection of connector (TH3, TH6/TH7) Open/short of outdoor unit thermistors 1 Disconnection or contact failure on the outdoor controller circuit board. Check (TH3, TH6, TH7, and TH8) of connectors connection of connector (CN6) on the outdoor Abnormal if open or short is detected...
  • Page 36 Abnormal point and detection method Judgment and action Check code Case To find out the detail history (latest) about U9 error, turn ON SW2-1, 2-2 and 2-6. Detailed Refer to "9-10. FUNCTION OF SWITCHES, CONNECTORS AND JUMPERS". codes Overvoltage error 1 Abnormal increase in power source 1 Check the field facility for the power •...
  • Page 37 From the previous page. Abnormal point and detection method Judgment and action Check code Case 12 Check the field facility for the power PFC error (Overvoltage/ Detailed 1 Abnormal increase in power supply. Undervoltage/Overcurrent) codes source voltage • PFC detected any of the fol- 2 Decrease in power source lowing: voltage, instantaneous stop.
  • Page 38 Abnormal points and detection method Case Judgment and action Check code Compressor overcurrent interruption 1 Stop valve of outdoor unit is 1 Open stop valve. Abnormal if overcurrent DC bus or com- closed. pressor is detected after compressor starts 2 Decrease of power supply voltage 2 Check facility of power supply.
  • Page 39 Check code Abnormal points and detection method Judgment and action Case Remote controller transmission error (E3)/signal receiving error (E5) 1 2 remote controller are set as 1 Set a remote controller to main, and the 1 Abnormal if remote controller could not “main.”...
  • Page 40 Check code Abnormal points and detection method Judgment and action Case Indoor/outdoor unit communication 1 Indoor/ outdoor unit connecting 1 Check disconnection or looseness of indoor/ error (Transmitting error) (Outdoor unit) wire has contact failure. outdoor unit connecting wire. 1 Abnormal if “0” receiving is detected 30 2 Defective communication circuit 2–4 Turn the power off, and on again to times continuously though outdoor con-...
  • Page 41 Check code Abnormal points and detection method Judgment and action Case Abnormal refrigerant circuit 1 Check refrigerant pipes for disconnection or 1 Disconnection of or leakage in During Cooling or Auto Cooling operation, leakage. refrigerant pipes when the following are regarded as 2 After the recovery of refrigerant, vacuum 2 Air into refrigerant piping failures when detected for one second.
  • Page 42 Check code Abnormal points and detection method Case Judgment and action NO ACK signal Common factor that has no Always try the following when the error relation with abnormality source 1. Transmitting side controller detects “A7” occurs. 1 The unit of former address abnormal if a message was transmitted does not exist as address but there is no reply (ACK) that a...
  • Page 43 From the previous page. Check code Abnormal points and detection method Case Judgment and action 4. If displayed address or attribute is Same as mentioned in “A7” of the previous 1 During group operation with indoor unit of multi- refrigerant remote controller, indoor unit detects page.
  • Page 44 Check code Abnormal points and detection method Case Judgment and action M-NET NO RESPONSE 1 Transmitting condition is 1 Check transmission waveform or noise on Abnormal if a message was transmitted repeated fault because of transmission wire. and there were reply (ACK) that message noise and the like.
  • Page 45 Factor Phenomena Countermeasure 4. Even controlling by the wireless 1 The pair number settings of the wireless remote 1 Check the pair number settings. remote controller, no beep is controller and indoor controller board are mismatched. heard and the unit does not start operating.
  • Page 46 Symptoms: “PLEASE WAIT” is kept being displayed on the remote controller. Inspection method and Diagnosis flow Cause troubleshooting Check the display time of “PLEASE WAIT” after turning on the main power. 6 minutes 2 minutes or more or less How long is “PLEASE WAIT” •...
  • Page 47 LED display of the indoor controller board Symptoms: Nothing is displayed on the remote controller 1 LED1 : LED2 : LED3 : Inspection method and Diagnosis flow Cause troubleshooting Check the voltage between S1 and S2 on the terminal block (TB4) of the indoor unit which is used to connect the indoor unit and the outdoor unit.
  • Page 48 LED display of the indoor controller board Symptoms: Nothing is displayed on the remote controller 2 LED1 : LED2 : LED3 : Inspection method and Diagnosis flow Cause troubleshooting Check the voltage between S1 and S2 on the terminal block (TB4) of the indoor unit which is used to connect the indoor unit and the outdoor unit.
  • Page 49 LED display of the indoor controller board Symptoms: Nothing is displayed on the remote controller 3 LED1 : LED2 : LED3 : — Inspection method and Diagnosis flow Cause troubleshooting Check the voltage of the terminal block (TB6) of the remote controller. 10 V DC to 16 V DC? •...
  • Page 50 • Before repair <Frequent calling from customers> Phone Calls From Customers How to Respond Note Unit does 1 The operating display of remote 1 Check if power is supplied to air conditioner. not operate controller does not come on. Nothing appears on the display unless power is at all.
  • Page 51 Phone Calls From Customers How to Respond Note Sound 4 A ticking sound is heard from 4 This is not a malfunction. comes out the outdoor unit sometimes. This is the sound which is heard when the fan of from the air the outdoor unit is controlling the airflow amount conditioner.
  • Page 52 Phone Calls From Customers How to Respond Note A white mist is expelled from the indoor unit. This is not a malfunction. This may occur when the operation gets started in the room of high humidity. Water or moisture is expelled from the outdoor When pipes or piping joints are cooled, they get unit.
  • Page 53 9-6. HOW TO CHECK THE PARTS PUHZ-SP100YKA.TH PUHZ-SP125VKA.TH PUHZ-SP125YKA.TH PUHZ-SP140VKA.TH PUHZ-SP140YKA.TH Parts name Check points Thermistor(TH3) Disconnect the connector then measure the resistance with a tester. <Liquid> (At the ambient temperature 10°C to 30°C) Thermistor (TH4) <Discharge> Normal Abnormal Thermistor (TH6) TH4, TH33 160 kΩ–410 kΩ...
  • Page 54 Check method of DC fan motor (fan motor / outdoor controller circuit board) Notes · High voltage is applied to the connecter (CNF1) for the fan motor. Pay attention to the service. · Do not pull out the connector (CNF1) for the motor with the power supply on. (It causes trouble of the outdoor controller circuit board and fan motor.) Self check Symptom : The outdoor fan cannot turn around.
  • Page 55 9-7. HOW TO CHECK THE COMPONENTS <Thermistor feature chart> Low temperature thermistors • Thermistor <Liquid> (TH3) • Thermistor <2-phase pipe> (TH6) • Thermistor <Ambient> (TH7) Thermistor R0 = 15 k" ± 3 % B constant = 3480 ± 2 % =15exp{3480( –...
  • Page 56 Linear expansion valve (1) Operation summary of the linear expansion valve • Linear expansion valve opens/closes through stepping motor after receiving the pulse signal from the outdoor controller board. • Valve position can be changed in proportion to the number of pulse signal. <Connection between the outdoor controller board and the linear expansion valve>...
  • Page 57 (3) How to attach and detach the coil of linear expansion valve <Composition> Linear expansion valve is separable into the main body and the coil as shown in the diagram below. Main body Stopper Coil Lead wire <How to detach the coil> Hold the lower part of the main body (shown as A) firmly so that the main body does not move and detach the coil by pulling it upward.
  • Page 58: Cooling

    9-8. EMERGENCY OPERATION (1) When the check codes shown below are displayed on outdoor unit or microcomputer for wired remote controller or indoor unit has a failure, but no other problems are found, emergency operation will be available by setting the emergency opera- tion switch (SWE) on indoor controller board to ON and short-circuiting the connector (CN31) on outdoor controller board.
  • Page 59: Heating

    (5) Operation data during emergency operation During emergency operation, no communication is performed with the indoor unit, so the data items needed for operation are set to the following values: Operation mode Remarks Operation data COOL HEAT Intake temperature (TH1) 20.5: —...
  • Page 60 9-9. TEST POINT DIAGRAM Outdoor controller circuit board PUHZ-SP100YKA.TH PUHZ-SP125VKA.TH PUHZ-SP125YKA.TH PUHZ-SP140VKA.TH PUHZ-SP140YKA.TH Manual defrost, CN51 CNDM detect history Demand control setting External signal output 1 to 2: Input of low-level sound priority mode record reset, • Compressor operating signal...
  • Page 61: Noise

    Outdoor noise filter circuit board PUHZ-SP100YKA.TH PUHZ-SP125YKA.TH PUHZ-SP140YKA.TH LI1, LI2, LI3, NI POWER SUPPLY LI1-LI2/LI2-LI3/LI3-LI1 : 400 V AC input LI1-NI/LI2-NI/LI3-NI : 230 V AC input (Connect to the terminal block (TB1)) Connect to the elec- trical parts box CNAC1, CNAC2 230 V AC (Connect to the outdoor controller...
  • Page 62 Outdoor power circuit board PUHZ-SP125VKA.TH Brief Check of POWER MODULE Usually, they are in a state of being short-circuited if they are broken. PUHZ-SP140VKA.TH Measure the resistance in the following points (connectors, etc.). If they are short-circuited, it means that they are broken.
  • Page 63: Noise

    Outdoor power circuit board PUHZ-SP100YKA.TH PUHZ-SP125YKA.TH Brief Check of POWER MODULE Usually, they are in a state of being short-circuited if they are broken. PUHZ-SP140YKA.TH Measure the resistance in the following points (connectors, etc.). If they are short-circuited, it means that they are broken. 1.
  • Page 64: Heating

    Outdoor M-NET board (optional) Switch for communication LED11 LED13 display between LED12 Outdoor unit Receiving CN2M M-NET and outdoor board Transmitting connecting display Connect to M-NET Serial communication with outdoor board LED2 Energizing display of M-NET board (5V power supply) LED1 SW11 SW12...
  • Page 65: Och671

    Action by the switch operation Type of Switch Function Effective timing Switch No function — — — Power failure Auto recovery No auto recovery When power supply ON automatic recovery 3,4,5,6 No function — — — Power consumption SW7-1 SW7-2 (Demand switch ON) Setting of demand 0% (Operation stop)
  • Page 66: Noise

    (2) Function of connector Action by open/ short operation Types Connector Function Effective timing Short Open Connector CN31 Start When power supply ON Emergency operation Normal (3)Special function (a) Low-level sound priority mode (Local wiring) By performing the following modification, operation noise of the outdoor unit can be reduced by about 3-4 dB. The low noise mode will be activated when a commercially available timer or the contact input of an ON/OFF switch is added to the CNDM connector (option) on the control board of the outdoor unit.
  • Page 67: Noise

    <Display function of inspection for outdoor unit> The blinking patterns of both LED1 (green) and LED2 (red) indicate the types of abnormality when it occurs. Types of abnormality can be indicated in details by connecting an optional part ‘A-Control Service Tool (PAC-SK52ST)’ to connector CNM on outdoor controller board.
  • Page 68: Och671

    Indication Error Outdoor controller board Detailed Check Contents Inspection method reference code* LED1 (Green) LED2 (Red) page Abnormality of comp. surface 3 blinking 1 blinking 1Check if stop valves are open. P.34 thermistor(TH33) and discharge 2Check if connectors (TH4, TH33, LEV-A and LEV-B) on outdoor controller board are not disconnected.
  • Page 69: Och671

    <Outdoor unit operation monitor function> [When optional part ‘A-Control Service Tool (PAC-SK52ST)’ is connected to outdoor controller board (CNM)] Digital indicator LED1 displays 2 digit number or code to inform operation condition and the meaning of check code by controlling DIP SW2 on ‘A-Control Service Tool’. Operation indicator SW2 : Indicator change of self diagnosis SW2 setting...
  • Page 70: Och671

    The black square ( ) indicates a switch position. Explanation for display Unit SW2 setting Display detail Discharge temperature (TH4) −20 to 217 −20 to 217 (When the discharge thermistor detects 100 : or more, hundreds digit, tens digit and ones digit are displayed by turns.) (Example) When 105 :;...
  • Page 71: Och671

    The black square ( ) indicates a switch position. SW2 setting Display detail Explanation for display Unit Discharge temperature (TH4) on error −20 to 217 occurring (When the temperature is 100 : or more, the −20 to 217 hundreds digit, tens digit and ones digit are displayed by turns.) (Example) When 130 :;...
  • Page 72: Och671

    The black square ( ) indicates a switch position. SW2 setting Display detail Explanation for display Unit 0 to 4 The number of connected indoor units (The number of connected indoor units are dis- played.) Unit 2 3 4 5 6 Capacity setting display Displayed as an outdoor capacity code.
  • Page 73: Och671

    The black square ( ) indicates a switch position. SW2 setting Display detail Explanation for display Unit Indoor setting temperature 17 to 30 17 to 30 °C 2 3 4 5 6 Outdoor 2-phase pipe (TH6) - 39 to 88 - 39 to 88 (When the temperature is 0: or less, “–”...
  • Page 74: Och671

    The black square ( ) indicates a switch position. SW2 setting Display detail Explanation for display Unit 0 to 500 (PUHZ-SP·VKA) DC bus voltage 0 to 1000 (PUHZ-SP·YKA) 0 to 500 (PUHZ-SP·VKA) (When it is 100 V or more, hundreds digit, tens 0 to 1000 (PUHZ-SP·YKA) digit and ones digit are displayed by turns.) 2 3 4 5 6...
  • Page 75: Och671

    The black square ( ) indicates a switch position. SW2 setting Display detail Explanation for display Unit Indoor pipe temperature / Liquid (TH2) - 39 to 88 on error occurring (When the temperature is 0 °C or less, “–” and - 39 to 88 temperature are displayed by turns.) (Example) When -15 °C;...
  • Page 76: Och671

    The black square ( ) indicates a switch position. Explanation for display Unit SW2 setting Display detail - 39 to 88 Indoor pipe temperature / Liquid (When the temperature is 0 °C or less, “–” and (TH2 (3)) temperature are displayed by turns.) Indoor 3 2 3 4 5 6 - 39 to 88...
  • Page 77: Function Setting

    FUNCTION SETTING 10-1. UNIT FUNCTION SETTING BY THE REMOTE CONTROLLER Each function can be set as necessary using the remote controller. The setting of function for each unit can only be done by the remote controller. Select function available from the <Table 1>. <Table 1>...
  • Page 78: Service Menu

    10-1-1. Selecting functions using the wired remote controller <PAR-31MAA> <Service menu> Maintenance password is required Select "Service" from the Main menu, and press the button. Main Main menu Maintenance Initial setting *At the main display, the menu button and select "Service" to make the Service maintenance setting.
  • Page 79 <Function setting> Select "Service" from the Main menu, and press the button. Test run Input maintenance info. Function setting Check Self check Select "Function setting" with the F1 or F2 button, and press the button. Set the indoor unit refrigerant addresses and unit numbers with the F1 Function setting Ref.
  • Page 80 10-1-2. Selecting functions using the wired remote controller <PAR-21MAA> First, try to familiarize yourself with the flow of the function selection procedure. In this section, an example of setting the room temperature detection position is given. For actual operations, refer to steps 1 to 0 . Setting number Refrigerant address Unit number...
  • Page 81 [Operating Procedure] 1 Check the setting items provided by function selection. If settings for a mode are changed by function selection, the functions of that mode will be changed accordingly. Check all the current settings according to steps 2 to 7 , fill in the "Check" column in Table 1, and then change them as necessary. For initial settings, refer to the indoor unit's installation manual. 2 Switch off the remote controller.
  • Page 82 10-1-3. Selecting functions using the wireless remote controller (Type C) Functions can be selected with the wireless remote controller. Function selection using wireless remote controller is available only for refriger- ant system with wireless function. Refrigerant address cannot be specified by the wireless remote controller. [Flow of function selection procedure] Flow of function selection procedure The flow of the function selection procedure is shown below.
  • Page 83 10-2. FUNCTION SELECTION OF REMOTE CONTROLLER 10-2-1. PAR-31MAA The functions of the function buttons change depending on the screen. Refer to the button function guide that appears at the bottom of the LCD for the functions they serve on a given screen.
  • Page 84 <Menu structure of PAR-31MAA> Press the button. MENU Main menu Move the cursor to the desired item with the buttons, and press the button. SELECT Vane · Louver · Vent. (Lossnay) High power Timer On / Off timer Auto-Off timer Filter information Error information Weekly timer...
  • Page 85 <Main menu list of PAR-31MAA> Setting and display items Setting details Vane · Louver · Vent. Use to set the vane angle. (Lossnay) • Select a desired vane setting from five different settings. Use to turn ON / OFF the louver. •...
  • Page 86 Setting and display items Setting details Initial setting Display Make the settings for the remote controller related items as necessary. details Clock: The initial settings are "Yes" and "24h" format. Temperature: Set either Celsius (°C) or Fahrenheit (°F). Room temp. : Set Show or Hide. Auto mode: Set the Auto mode display or Only Auto display.
  • Page 87 10-2-2. PAR-21MAA Normal display (Display when the air conditioner is not running) Setting language (English) Hold down the button and press the button for 2 seconds. Hold down the button and press the button for 2 seconds. Press the operation mode button. Press theTIMER MENU button.
  • Page 88 The setting of the following remote controller functions can be changed using the remote controller function selection mode. Change the setting when needed. Item 1 Item 2 Item 3 (Setting content) 1.Change Language Language setting to display • Display in multiple languages is possible. ("CHANGE LANGUAGE") 2.Function limit (1) Operation function limit setting (operation lock) ("LOCKING FUNCTION")
  • Page 89: Monitoring The Operation Data By The Remote Controller

    MONITORING THE OPERATION DATA BY THE REMOTE CONTROLLER 11-1. HOW TO "MONITOR THE OPERATION DATA" 11-1-1. PAR-31MAA Details on the operation data including each thermistor temperature and error history can be confirmed with the remote controller. Select "Service" from the Main menu, and press the button.
  • Page 90 11-1-2. PAR-21MAA 12-1. HOW TO "MONITOR THE OPERATION DATA" • Turn on the [Monitoring the operation data] Example) Request code "004" Discharge temperature 69°C Refrigerant address "00" A: Maintenance mode B: Refrigerant address C: Data display area D: Request code display area (1) Press the button for 3 seconds so that [ Maintenance mode] appears on the screen (at A ).
  • Page 91 11-2. Request code list Certain indoor/outdoor combinations do not have the request code function; therefore, no request codes are displayed. Description Request content Unit Remarks (Display range) Operation state Refer to "11-2-1.Detail Contents in Request Code". – Compressor-Operating current (rms) 0 –...
  • Page 92 Description Request content Unit Remarks (Display range) Indoor unit-Control state – Refer to "11-2-1.Detail Contents in Request Code". Outdoor unit-Control state – Refer to "11-2-1.Detail Contents in Request Code". Compressor-Frequency control state Refer to "11-2-1.Detail Contents in Request Code". – Outdoor unit-Fan control state Refer to "11-2-1.Detail Contents in Request Code".
  • Page 93 Description Request content Unit Remarks (Display range) Error history 1 (latest) Displays the history. (" - - " is displayed if no history is present.) Code Error history 2 (second to last) Displays the history. (" - - " is displayed if no history is present.) Code Error history 3 (third to last) Displays the history.
  • Page 94 Description Request content Unit Remarks (Display range) Indoor-Fan operating time 0 – 9999 1 hour (After filter is reset) Indoor-Total operating time 0 – 9999 10 hours (Fan motor ON time) Indoor fan output value (Sj value) 0 – 255 Fan control data –...
  • Page 95 11-2-1. Detail Contents in Request Code Example) Request code "004" Discharge temperature 69 : Refrigerant address "00" A: Maintenance mode display B: Refrigerant address C: Data display area D: Request code display area [Operation state] (Request code :" 0") Relay output state Power currently Data display Display...
  • Page 96 [Fan control state] (Request code :" 53 ") Data display Fan step correction value by heatsink temperature overheat prevention control Fan step correction value by cool condensation temperature overheat prevention control Display Correction value - (minus) – 1 [Actuator output state] (Request code :"54") Data display Actuator output state 1 Actuator output state 2...
  • Page 97 [Contact demand capacity] (Request code : " 61") Setting content Data display Display Setting value Setting content 100% [External input state] (Request code : "62") Input state : Input present Data display Contact demand Silent mode Spare 1 Spare 2 Display Input state input...
  • Page 98 [Indoor unit – Capacity setting information] (Request code : "163" ) Data display Display Capacity setting state Display Capacity setting state See the table on the right. [Wireless pair No. (indoor control board side) setting] (Request code :" 165") Data display Display Pair No.
  • Page 99: Easy Maintenance Function

    EASY MAINTENANCE FUNCTION 12-1. SMOOTH MAINTENANCE 12-1-1. PAR-30MAA/PAR-31MAA Maintenance data, such as the indoor/outdoor unit’s heat exchanger temperature and compressor operation current can be displayed with “Smooth maintenance”. This cannot be executed during test operation. Depending on the combination with the outdoor unit, this may not be supported by some models. Select "Service"...
  • Page 100 12-1-2. PAR-21MAA ● Reduces maintenance work drastically. ● Enables you to check operation data of the indoor and outdoor units by remote controller. Furthermore, use of maintenance stable-operation control that fixes the operating frequency, allows smooth inspection, even for inverter models. Smooth Mainte- Discharge temperature 64°C ●...
  • Page 101 ● Data measurement When the operation is stabilized, measure operation data as explained below. (4) Press the [TEMP] buttons ( ) to select the desired refrigerant address. [Screen (5) Select the type of data to be displayed. After selecting, go to step (6). Compressor information button MENU...
  • Page 102 <Guide for opration condition> Check Points Inspection item Result Breaker Good Retightened Enter the temperature differences between into Terminal block Outdoor Unit Good Retightened the graph given below. Indoor Unit Good Retightened Operation state is determined according to the plotted areas on (Insulation resistance) M"...
  • Page 103: 13 Disassembly Procedure

    13 DISASSEMBLY PROCEDURE PUHZ-SP100YKA.TH PUHZ-SP125VKA.TH PUHZ-SP125YKA.TH PUHZ-SP140VKA.TH PUHZ-SP140YKA.TH OPERATING PROCEDURE PHOTOS/FIGURES 1. Removing the service panel and top panel Photo 1 Top panel fixing screws Top panel (1) Remove 3 service panel fixing screws (5 × 12) and slide the hook on the right downward to remove the service Service panel panel.
  • Page 104 From the previous page. OPERATING PROCEDURE PHOTOS/FIGURES (8) Remove 2 electrical parts box fixing screws (4 × 10) and detach the electrical parts box by pulling it upward. The electrical parts box is fixed with 2 hooks on the left and 1 hook on the right.
  • Page 105 From the previous page. OPERATING PROCEDURE PHOTOS/FIGURES 4. Disassembling the electrical parts box (YKA type) Photo 9 Electrical parts box (1) Disconnect all the connectors on the controller circuit board. (2) Remove the screw 1, that fix the plate equipped with the outdoor controller circuit board, and the electrical parts box.
  • Page 106 PHOTOS/FIGURES OPERATING PROCEDURE 6. Removing the thermistor <Ambient> (TH7) Photo 13 Thermistor <Ambient> (TH7) (1) Remove the service panel. (See Photo 1) (2) Remove the top panel. (See Photo 1) (3) Disconnect the connector TH7/6 (red) on the controller circuit board in the electrical parts box. (4) Loosen the 2 wire clamps on top of the electrical parts box.
  • Page 107 OPERATING PROCEDURE PHOTOS/FIGURES Photo 18 8. Removing LEV coil (1) Remove the service panel. (See Photo 1) (2) Remove the top panel. (See Photo 1) (3) Remove the LEV coil by sliding the coil upward. (See Photo 19) (4) Disconnect the connectors, LEV-B (RD) on the controller circuit board in the electrical parts box.
  • Page 108 Note: Recover refrigerant without spreading it in the air. HEAD OFFICE : TOKYO BUILDING, 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN CCopyright 2017 MITSUBISHI ELECTRIC CORPORATION Published: Sep. 2017 No.OCH671 Specifications are subject to change without notice.

Table of Contents