1.10 Instructions for installation and connection of the unit
A
Liquid cooling line.
B
Gas cooling line.
H
Vertical distance between units (max. 30 m).
Total pipe length (vertical + horizontal sec‐
L
tions). Laid and in one direction.
1
Outdoor unit.
2
Indoor unit.
A
Liquid cooling line.
B
Gas cooling line.
H
Vertical distance between units (max. 30 m).
Total pipe length (vertical + horizontal sec‐
L
tions). Laid and in one direction.
1
Outdoor unit.
2
Indoor unit.
Maximum length L: this is the sum of the lengths of all straight horizontal and vertical sections in one
direction, whether they hold liquid or gas.
Maximum equivalent length L
in one direction, whether they hold liquid or gas, plus the equivalent length of the accessories, basically
elbow joints and bends.
Equivalent length of accessories in metres
Outer pipe diameter
3/8"
1/2"
5/8"
3/4"
7/8"
1 ⅛"
1 ⅜"
1 ⅝"
N O T E
The 45° elbow joints and bends (used in drain traps, for example) have half the equivalent length of the
90° bends.
34
: this is the sum of the lengths of all straight horizontal and vertical sections
E
Short elbow joint radius
0,30
0,40
0,50
0,50
0,60
0,70
1,00
1,20
1
A
L
B
H
2
B
A
L
H
90° bend (Long radius)
0,20
0,30
0,40
0,40
0,50
0,60
0,70
0,80
2
1