Table P58: 006-060 Correction Factors for Variation in Entering Air Temperature
Cooling
Cooling
Cooling
Entering
Capacity
Input
Air WB F
Watts
49.4
0.722
0.893
56.3
0.836
0.937
60.3
0.903
0.963
63.2
0.951
0.981
66.2
1.000
1.000
72.1
1.098
1.038
77.1
1.181
1.069
* = Sensible equals total capacity
84
Performance Data

Correction Factors

Sensible vs Entering Dry Bulb
Multipliers
65.6
70.6
75.6
80.6
*
*
*
0.799
0.964
*
0.641
0.841
1.016
1.097
0.504
0.728
0.924
1.097
0.593
0.809
1.000
0.538
0.761
0.519
Heating
Entering
85.6
Air DB F
*
*
53.0
*
*
58.0
*
63.0
*
68.0
1.169
73.0
0.960
78.0
0.741
83.0
Heating
Heating
Capacity
Input
Watts
1.030
0.878
1.020
0.919
1.010
0.959
1.000
1.000
0.990
1.041
0.980
1.081
0.970
1.122