Trane GEH 006 Manual page 11

High efficiency horizontal and vertical water-source comfort system, 1/2 - 5 tons - 60 hz, 12 1/2 - 25 tons - 60 hz
Table of Contents

Advertisement

Figure 19: Internal air-to-refrigerant coil placement (GEH)
The sound package for the horizontal unit includes:
Table 2: Sound Package (1/2 through 5-ton units ONLY)
Enhanced Sound Attenuation
Package
18-gauge compressor enclosure
18-gauge single wall front panel
lined compressor enclosure with
1/2-inch cabinet insulation
compressor discharge muffler
12-gauge compressor/water-to-refrig-
erant heat exchanger pan with second
stage of vibration isolation
compressor vibration isolation
water-to-refrigerant heat exchanger
vibration isolation
lengthwise unit base stiffeners
WSHP-PRC001-EN
Features and
Benefits
Air-to-Refrigerant Coil
The air-to-refrigerant heat exchanger is constructed of staggered
copper tubes with die-formed corrugated lanced aluminum fins.
The fins are then mechanically bonded to the tubes through ex-
pansion.
The coil is placed internal of the unit design for model
GEH to assure no fin surface damage during shipment,
jobsite storage, or installation.
The internal placement of the coil on the horizontal con-
figuration provides an option of a dual filtration applica-
tion. With dual filtration to the GEH unit, maintenance to
the filter is significantly less than with a single filtration
system.
The maximum working pressure for both the GEH and
GEV coils is 450 psig. It is designed for maximum capac-
ity with an additional benefit of physical unit size reduc-
tion.
Coil specifications for both GEH and GEV may be found on
in the General Data section on page 48 of this catalog. See
Figure 19 for internal air to refrigerant coil placement.
Deluxe Sound Attenuation
Package
16-gauge compressor enclosure
16-gauge single wall front panel
lined compressor enclosure with
1/2-inch cabinet insulation
compressor discharge muffler
12-gauge compressor/water-to-refrig-
erant heat exchanger pan with second
stage of vibration isolation
compressor vibration isolation
water-to-refrigerant heat exchanger
vibration isolation
lengthwise unit base stiffeners
3/32-inch foam gasket sealant placed
around the compressor and end panel
perimeter
Sound Attenuation Package
Testing of conventional units has iden-
tified that the sound radiated by the
casing of the unit is an important com-
ponent of the sound that reaches occu-
pants, especially when the unit is
located directly over the occupied
space.
This sound reduction package reduces
radiated noise from the cabinet. Trane
double-isolates the compressor and
single-isolates the co-axial coil in the
unit. This design absorbs the vibration
that contributes to radiated sound
For sound critical spaces, an
enhanced sound package as de-
scribed in Table 2 provides additional
attenuation.
Complete sound data taken in accor-
dance with ARI 260 is available for all
1/2 through 5-ton units. The test data
reflects multi-speed fan motor along a
single system curve. (See sound per-
formance data on Page 107.)
11

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents