Waterside Economizer Performance - Trane GEH 006 Manual

High efficiency horizontal and vertical water-source comfort system, 1/2 - 5 tons - 60 hz, 12 1/2 - 25 tons - 60 hz
Table of Contents

Advertisement

Performance data is tabulated for cooling at 80 F DB/67 F WB entering air and 45 F entering fluid at ARI 410 rated SCFM.
Table W1: Waterside Economizer Performance Data (1/2 through 5 Tons)
Input Data
Tonnage
Model
SCFM
of Heat
GEH
Pump
0.50
006
190
0.75
009
285
1.00
012
380
1.25
015
460
1.50
018
570
2.00
024
760
2.50
030
900
3.00
036
1140
3.50
042
1330
4.00
048
1520
5.00
060
1900
Table W2: Waterside Economizer Performance Data (12 1/2 through 25 Tons)
Input Data
Ton-
Model
SCFM
nage of
GEV
Heat
Pump
12.50
150
5000
15.00
180
6000
20.00
240
8000
25.00
300
10000
WSHP-PRC001-EN
Performance Data
Waterside Economizer
GPM
Total
Sensible
Capacity
Capacity
(MBH)
1.2
5.83
1.5
6.3
1.7
6.65
1.7
7.86
2.1
8.49
2.3
8.76
2.2
9.75
2.8
10.6
3.1
11.03
2.8
11.44
3.5
12.33
3.8
12.69
3.3
16.27
4.2
17.61
4.6
18.05
4.4
20.25
5.5
21.58
6.1
22.19
5.5
23.27
6.9
24.71
7.6
25.28
6.6
29.28
8.3
31.47
9.1
32.2
7.8
32.88
9.7
34.81
10.7
35.67
8.8
39.77
11
42.44
12.1
43.65
11.6
47.59
14.5
50.66
16
51.87
GPM
Air Velocity
Total
(SFPM)
Capacity
(MBH)
27.5
308
160.4
35
308
177.4
38.75
308
184.0
33
370
187.3
42
370
205.4
46.5
370
212.3
44
438
241.7
56
438
263.0
62
438
271.3
55
548
280.8
70
548
299.0
77.5
548
306.8
Output Data
LVG. Air
LVG. Air
DB
WB
(MBH)
(Deg F)
(Deg F)
4.28
59.4
57.3
4.6
58.5
56.5
4.61
57.8
55.8
5.91
61.1
58.4
6.14
60.3
57.7
6.25
60.0
57.3
7.41
62.2
59.1
7.72
61.4
58.3
7.91
61.0
57.9
8.68
62.7
59.3
9.03
62.1
58.7
9.19
61.7
58.4
11.71
61.2
58.1
12.25
60.4
57.3
12.42
60.1
57.0
14.65
62.4
58.7
15.21
61.7
0.2
15.43
61.4
57.9
16.81
62.9
59.0
17.38
62.3
58.5
17.64
62.1
58.3
21.57
62.7
59.1
22.41
62.0
58.4
22.2
61.8
58.2
24.88
63.4
59.4
25.05
62.8
58.9
25.37
62.6
58.7
29.11
62.5
58.9
30.25
61.8
58.3
30.69
61.5
58.0
34.73
63.3
59.3
35.94
62.7
58.7
36.39
62.5
58.5
Output Data
Sensible
LVG. Air
Capacity
DB
(MBH)
(Deg F)
120.6
58.0
127.3
56.7
130.0
56.2
141.4
58.5
148.5
57.4
151.3
56.9
183.4
59.0
191.8
58.1
195.1
57.7
219.5
60.1
228.4
59.3
232.1
58.9
Standard
LVG.Flui
Fluid PD
APD
d Temp.
(FT H
(IN WG)
Degree F
0.03
54.7
0.23
0.03
53.4
0.34
0.03
52.8
0.42
0.07
54.2
0.42
0.07
53.1
0.60
0.07
52.6
0.71
0.11
53.8
0.65
0.11
52.6
0.99
0.11
52.1
1.18
0.15
53.1
0.99
0.15
52.0
1.46
0.15
51.7
1.69
0.12
54.8
1.36
0.12
53.4
2.08
0.12
52.8
2.45
0.19
54.2
2.26
0.19
52.8
3.4
0.19
52.3
4.03
0.25
53.4
3.4
0.25
52.1
5.01
0.25
51.6
5.95
0.19
53.8
2.39
0.19
52.6
5.25
0.19
52.1
6.19
0.25
53.4
4.70
0.25
52.2
6.92
0.25
51.6
8.24
0.17
54.0
1.24
0.17
52.7
1.86
0.17
52.2
2.21
0.24
53.2
2.04
0.24
52.0
3.05
0.24
51.5
3.65
LVG. Air
Standard
LVG.Flui
WB
APD
d Temp.
(Deg F)
(IN WG)
Degree F
56.9
0.175
56.6
55.7
0.183
55.1
55.2
0.185
54.5
57.2
0.234
56.3
56.1
0.242
54.8
55.7
0.246
54.1
57.5
0.305
56.0
56.6
0.315
54.4
56.2
0.319
53.7
58.2
0.52
55.2
57.5
0.52
53.5
57.3
0.53
52.9
O)
2
Fluid PD
(FT H
O)
2
6.93
11.22
13.75
9.80
15.87
19.46
8.56
13.86
16.99
9.76
15.82
19.39