Trane GEH 006 Manual page 77

High efficiency horizontal and vertical water-source comfort system, 1/2 - 5 tons - 60 hz, 12 1/2 - 25 tons - 60 hz
Table of Contents

Advertisement

Table P-43: GEV 180 Heating Performance
Performance data is tabulated for heating at 68 F DB entering air at ARI/ISO 13256-1 rated CFM.
For conditions other than what is tabulated, multipliers must be used to correct performance. See the fan correction factors Table for CFM
other than rated and the heating correction factors for variations in entering air temperature. Data shown in bold type is performance data
at ARI/ISO 13256-1 WLHP and GLHP water only conditions. Antifreeze correction factors may be found on page 108
RATED ESP (in. H20):
EWT
GPM
Htg Cap
Mbtuh
22.5
112.2
30.0
115.0
25
37.5
117.3
45.0
119.1
52.5
120.6
22.5
123.8
30.0
127.2
GLHP
37.5
130.0
32
45.0
132.3
52.5
134.0
22.5
147.2
30.0
152.0
45
37.5
156.9
45.0
160.1
52.0
161.4
22.5
166.7
30.0
172.6
55
37.5
177.5
45.0
181.4
52.5
184.6
22.5
193.7
30.0
201.3
WLHP
37.5
207.6
68
45.0
212.6
52.5
216.7
22.5
208.9
30.0
217.5
75
37.5
224.5
45.0
230.3
52.5
234.9
22.5
233.7
30.0
243.9
86
37.5
252.4
45.0
259.3
52.5
264.8
Table P44: 180 Correction Factor for Variation in Entering Air Temperature
Cooling
Cooling
Cooling
Entering
Capacity
Input
Air WB F
Watts
49.4
0.930
0.988
56.3
0.931
0.988
60.3
0.932
0.988
63.2
0.959
0.993
66.2
1.000
1.000
72.1
1.100
1.016
77.1
1.213
1.003
Table P45: 180 Fan Correction Factors
Entering
Cooling
Sensible
SCFM
Capacity
Capacity
4800
0.967
0.896
5400
0.985
0.949
6000
1.000
1.000
6600
1.014
1.048
7200
1.026
1.096
WSHP-PRC001-EN
Performance Data
180-Heating
0.35
Absorb
Power
LWT
Mbtuh
kW
76
10.62
18.2
78.5
10.69
19.8
80.6
10.74
20.7
82.3
10.79
21.3
83.7
10.82
21.8
86.6
10.90
24.3
89.7
10.98
26.0
92.3
11.05
27.1
94.4
11.10
27.8
96
11.14
28.3
108.1
11.46
35.4
112.5
11.57
37.5
117
11.69
38.8
119.9
11.77
39.7
121.1
11.80
40.4
126
11.93
43.8
131.4
12.07
46.2
135.9
12.20
47.8
139.4
12.30
48.8
142.4
12.37
49.6
150.7
12.61
54.6
157.6
12.81
57.5
163.3
12.97
59.3
167.9
13.11
60.5
171.6
13.22
61.5
164.5
13.01
60.3
172.3
13.24
63.5
178.6
13.44
65.5
183.9
13.60
66.8
188
13.73
67.8
186.9
13.70
69.3
196.2
13.99
72.9
203.8
14.25
75.1
209.9
14.46
76.6
214.9
14.63
77.8
Sensible vs Entering Dry Bulb
Multipliers
65.6
70.6
75.6
0.989
1.055
1.120
0.809
1.008
1.121
0.647
0.846
1.045
0.527
0.726
0.926
0.601
0.801
0.551
Cooling
Heating
Heating
Input
Capacity
Input
Watts
Watts
0.994
0.986
1.060
0.997
0.993
1.026
1.000
1.000
1.000
1.002
1.005
0.979
1.004
1.010
0.962
RATED GPM:
45.0
RATED CFM:
6000
Feet
PSID
SCFM
ISO Cap
Head
Head
Mbtuh
7.0
3.01
109.4
11.1
4.79
112.2
6000
15.8
6.85
114.5
21.2
9.19
116.3
27.2
11.77
117.8
7.0
3.01
121.0
11.1
4.79
124.4
6000
15.8
6.86
127.2
21.2
9.19
129.5
27.2
11.78
131.2
7.0
3.01
144.4
11.1
4.79
149.2
6000
15.8
6.86
154.1
21.2
9.19
157.3
26.8
11.60
158.6
7.0
3.01
163.9
11.1
4.78
169.8
6000
15.8
6.85
174.7
21.2
9.19
178.6
27.2
11.77
181.8
6.9
3.01
190.9
11.0
4.78
198.5
6000
15.8
6.84
204.8
21.2
9.17
209.8
27.1
11.75
213.9
6.9
3.00
206.1
11.0
4.77
214.7
6000
15.8
6.83
221.7
21.1
9.16
227.5
27.1
11.73
232.1
6.9
2.99
230.9
11.0
4.76
241.1
6000
15.7
6.81
249.6
21.1
9.13
256.5
27.0
11.70
262.0
Heating
Entering
80.6
85.6
Air DB F
1.185
1.251
53.0
1.187
1.253
58.0
1.188
1.254
63.0
1.125
1.255
68.0
1.000
1.200
73.0
0.751
0.951
78.0
0.545
0.747
83.0
.
MINIMUM CFM:
4800
MAXIMUM CFM:
7200
ISO
ISO COP
Power
kW
9.90
3.24
10.07
3.26
10.29
3.26
10.57
3.23
10.90
3.17
10.18
3.48
10.37
3.52
10.60
3.52
10.88
3.49
11.22
3.43
10.73
3.94
10.96
3.99
11.24
4.02
11.55
3.99
11.85
3.92
11.20
4.29
11.46
4.34
11.75
4.36
12.07
4.34
12.45
4.28
11.88
4.71
12.19
4.77
12.52
4.79
12.89
4.77
13.29
4.72
12.29
4.92
12.63
4.98
12.99
5.00
13.38
4.98
13.81
4.93
12.97
5.22
13.38
5.28
13.80
5.30
14.23
5.28
14.70
5.22
Heating
Heating
Capacity
Input
Watts
1.034
0.890
1.023
0.925
1.011
0.961
1.000
1.000
0.989
1.041
0.979
1.084
0.969
1.129
77