Adjustable Speed Pulse Output - Delta DVP-PLC Applications Manual

Table of Contents

Advertisement

API
Mnemonic
157
D
PLSV
Type
Bit Devices
OP
X
Y
S
D
*
1
D
*
2
Operands:
S: Pulse output frequency
the signal of rotation direction
Explanations:
1.
See remarks for the setting range of S, D
2.
Flag: see remarks of API 155 ABSR and API 158 DDRVI for more details.
3.
S is the designated pulse output frequency. The 16-bit instruction can designate its range 0 ~ +32,767Hz, 0 ~
-32,768Hz. The ranges designated by 32-bit instruction are 0 ~ +200,000Hz and 0 ~ -200,000Hz. "+/-" signs
indicate forward/backward directions. During the pulse output, the frequency can be changed, but not the
frequencies of different directions.
4.
D
is the pulse output device. EH series MPU can designate Y0 and Y2 and EH2/SV series MPU can designate
1
Y0, Y2, Y4 and Y6.
5.
The operation of D
2
6.
PLSV instruction does not have settings for acceleration and deceleration. Please use API 67 RAMP for the
acceleration and deceleration of pulse output frequency.
7.
During the pulse output executed by PLSV instruction, the drive contact turning Off will result in the immediate
stop of the output without going through a deceleration.
8.
When the absolute value of the input frequency during the execution of DPLSV is bigger than 200KHz, the
output will operate at 200KHz.
9.
For EH/EH2/SV series MPU, D1222, D1223, D1383 and D1384 are the time differences sent between the
direction setup signal and pulse output points of CH0, CH1, CH2 and CH3.
10. For EH/EH2/SV series MPU, M1305, M1306, M1532 and M1533 are the flags of the direction signals of CH0,
CH1, CH2 and CH3. When S is "+", the output will operate towards a forward direction and the flag will go Off.
When S is "-", the output will operate towards a backward direction and the flag will go On.
Program Example:
When M10 = On, Y0 will output pulses at 20KHz. Y5 = On indicates forward pulses.
M10
PLSV
K20000
DVP-PLC Application Manual
Operands
M
S
K
H KnX KnY KnM KnS T
*
*
*
*
*
ES EX SS SA SX SC EH SV ES EX SS SA SX SC EH SV ES EX SS SA SX SC EH SV
D
: Pulse output device (please use transistor output module)
1
and D
1
corresponds to the "+" or "-" of S. When S is "+", D
Y0
Y5
9 Application Instructions API 150-199
Function

Adjustable Speed Pulse Output

Word Devices
C
*
*
*
*
*
PULSE
.
2
Controllers
ES/EX/SS SA/SX/SC EH/SV
Program Steps
D
E
F
PLSV: 7 steps
*
*
*
DPLSV: 13 steps
16-bit
D
will be On; when S is "-", D
2
32-bit
: Output device for
2
will be Off.
2
9-23