PGM Output Types [01], [03], [04], [05]-[08], and [17]-[18]
1
Not Used
2
Not Used
3
Output Level
PGM Output Types [03], and [19]-[22].ON
4
Output Options
PGM Output Types [19]-[22].
5
Access Code Options
PGM Output Types [09] System Trouble
1
Service Required
2
AC Fail
3
Telephone Line Fault
4
Communications (Failure)
5
Zone (Fire) Fault
6
Zone Tamper
7
Zone Low Battery
8
Loss of Clock
PGM Output Types [10] System Event
1
Burglary
2
Fire
3
Panic
4
Medical
5
Supervisory
6
Priority
7
Holdup
8
Output Options
[551]-[564] PGM Partition Assignment)
The PC5020 has a 8-bit toggle field per output that determines
which partitions the output is assigned to (outputs PGM 1-14).
Each bit corresponds to a Partition in each PGM's toggle Mask.
50
[501]-[515] PROGRAMMABLE OUTPUT ATTRIBUTES
NOTE: This option must be off to ensure proper PGM operation.
NOTE: This option must be off to ensure proper PGM operation.
ON
The output will activate (switch to Ground) when the event occurs.
OFF
The output will de-activate (switch to open) when the event occurs.
ON
Output Pulsed. The output will activate for the duration programmed in for the PGM
Output Timer in Section [164]. This default period is five seconds.
OFF
Output On/Off. The output will toggle between on and off when the corresponding
[*][7] command is entered.
ON
Access Code Required for Activation.
OFF
No Access Code Required for Activation. Attribute 3 is available for all Output types.
Delay, Instant, Interior, Stay/Away, and 24 Hour Burg Zone Types
[F] Key, Fire Zone
[P] Key and Panic zones
[A] Key, Medical and Emergency zones
Supervisory, Freeze and Water zones
Gas, Heat, Sprinkler and 24 Hour Latching Tamper zones
Holdup Zones and Duress Alarms
ON
Output Follows PGM Timer. The output will activate for the period of time pro-
grammed for the PGM Output Timer.
OFF
Output is Latched. The output will be active until a valid access code is entered.
NOTE: If a System Event PGM is programmed to follow the Command Output Timer, all
attributes must be enabled.
NOTE: These are the attributes available for the System Event PGM option. The output
will activate if any of the corresponding alarm types occur on the system.
This field is supported by PGMs that have multiple partition
capabilities (i.e. Command Outputs, Away Arming) It does not
affect System outputs (i.e. Ground Start Pulse).