Framing And Finishing; Clearance Requirements; Combustible Mantels - Regency Zero Clearance Direct Vent Gas Fireplace P121/P131-LP2 Specifications

Zero clearance direct vent gas fireplace

Advertisement

P121-P131 Gas Fireplace

Framing and Finishing

1)
Determine the total thickness of facing material (e.g. drywall plus
ceramic tiles) to allow the fi nished surface to be fl ush with the front
of the unit. Total facing thickness can vary from 1/2" (13mm) to 1-¼"
(32mm) thick.
2)
Frame in the enclosure for the unit with framing material.
3)
For exterior walls, insulate the enclosure to the same degree as
the rest of the house, apply vapor barrier and drywall, as per local
installation codes. (Do not insulate the fi replace itself.)
4)
The top of the unit must not be closer than 36" (990mm) to the
ceiling.
5)
Combustible material may be brought up to the top and
sides of the unit and be covered with ceramic tiles, bricks,
rock or other suitable combustible finishing materials.
Note: The unit does not have to be completely enclosed in a
chase. The clearance on top of the unit is 0" to the standoffs
so combustible building materials can be laid directly on top
of the standoffs. You must maintain proper clearances from
the vent to combustible materials (See Below).
6)
Use metal studs for framing where the minimum clearance from
the vent to combustible material cannot be maintained.

Clearance Requirements

D
C
A
B
Clearance:
Dimension
A: Mantel Height
3" (76mm)
B: Sidewall
0" (0mm)
3" (76mm)
C: Ceiling
36" (914mm)
D: Mantel Depth
12" (305mm)
E: Alcove Width
See Parallel Wall Clearances.
F: Alcove Depth
36" (914mm)
Top of Hearth must not be higher than the base of the fi rebox.
70
F
B
E
Measured From:
Minimum (Additional on this page)
Side of installed front
On P121-2 See-Thru
3" clearance opposite vent.
Top of installed unit
Maximum (Additional on this page)
Front to back wall (Maximum)
Gas Fireplaces
Parallel Wall Clearances
Unless otherwise stated the clearances listed below are Minimum
distances to combustible materials. Unit pictured is a P131
Parallel Wall Clearances
Min distance from glass to a parallel wall
Vent Clearances
Horizontal - Top
Horizontal - Side
Horizontal - Bottom
Vertical
WARNING
Failure to maintain required clearances is a major cause of
chimney related fi res. Installation of this fi replace must comply
with these clearances.

Combustible Mantels

Because of the extreme heat this fi replace emits, the mantel
clearances are critical. Combustible mantel clearances from top of
the louvers are shown in the diagram below. Mantel may be installed
anywhere in the shaded area or higher.
Note: If the fi replace is installed
without the 3" Extension Trim,
the facing material must be
non combustible up to 8"
above the unit.
Mantel Clearances
A
Front
36" (914mm)
Note: If desired a non-combustible mantel may be installed at a
lower height.
Note: Ensure the paint that is used on the mantel and the facing
is "heat resistant" or the paint may discolour.
June 2007 Regency Product Specifi cations Book
P121(LC/RC)/131
36" (914mm)
Clearance Dimension
2-1/2" (64mm)
1-1/2" (38mm)
1-1/2" (38mm)
1-1/4" (32mm)
Mantel Clearances
0
12
10
8
6
4
2
Drywall
12" (305mm)
Header
Standoff
B
3 ½" (89mm)
3" Extension Trim
C
0
Top of
A
Unit
Side View
B
C
7" (178mm)
3" (76mm)

Advertisement