Table 6. Type CS403 Regulator and Integral Monitor Outlet Pressure Ranges
PRIMARY REGULATOR
Setpoint
TYPE
In. w.c.
mbar
4
10
5
12
7
17
11
27
14
35
CS403
18
45
1 psig
69
2 psig
138
3 psig
207
4 psig
276
5 psig
345
1. Integral Monitor setpoints shown represent the minimum setpoint difference between the Integral Monitor and the Primary regulator. Higher monitor setpoints can be chosen, e.g., for
Primary regulator setpoint of 7 in. w.c. / 17 mbar, the Integral Monitor can also be set at 14, 21 in. w.c., 1 psig / 35, 52, 69 mbar or higher.
REGULATOR
Setpoint
TYPE
In. w.c.
mbar
4
5
7
11
14
0.65 psig
0.72 psig
CS404
1 psig
1.5 psig
103
2 psig
138
3 psig
207
4 psig
276
5 psig
345
5.5 psig
380
1. For Types CS404IT and CS404ET equipped with Token Relief, if Non-Factory slam-shut OPSO setpoints are specified, they must not encroach on the Token Relief Start-to-Discharge
values provided in Table 4 of the CS400 Bulletin.
Table 8. Type CS404 Regulator and Slam-shut OPSO and UPSO Pressure Ranges
REGULATOR
Setpoint
Spring Range
TYPE
psig
mbar
psig
0.51
35
0.36 to 0.51 25 to 35
0.65
45
0.45 to 0.70 30 to 48
0.72
50
0.65 to 1
1
69
1.5
103
CS404
1 to 2
2
138
3
207
4
276
2 to 5.5
5
345
5.5
380
1. For Types CS404IT and CS404ET equipped with Token Relief, if Non-Factory slam-shut OPSO setpoints are specified, they must not encroach on the Token Relief Start-to-Discharge
values provided in Table 4 of the CS400 Bulletin.
Spring Part
Spring
Number
Color
GE30198X012
Red
GE30195X012
Purple
GE30188X012
Gold
GE30189X012
Blue
GE30224X012
Unpainted
GE30196X012
Green
GE30225X012
Orange
GE30190X012
Black
GE30197X012
GE30197X012
Yellow
GE30197X012
Table 7. Type CS404 Regulator and Slam-shut OPSO Pressure Ranges