Daikin FH15CBV1L Technical Manual page 81

Ceiling exposed
Table of Contents

Advertisement

Diagnostic Guidelines
By means of pressure reading :
Data
Circuit
High side
Low side
High side
Low side
High side
Low side
High side
Low side
High side
Low side
79
Pressure
Probable cause
1. Overcharged with refrigerant.
2. Non-condensable gases in refrigerant circuit (e.g. air)
3. Obstructed air-intake / discharge.
4. Hot air short circuiting in outdoor unit.
1. Poor compression / no compression (compressor
defective)
2. Reversing valve leaking.
1. Undercharged with refrigerant.
2. Refrigerant leakage.
3. Air filter clogged / dirty (indoor unit).
4. Indoor fan locked / seized.
1. Outdoor fan blocked (cooling).
2. Outdoor coil dirty (cooling).
3. Non-condensable gases in refrigerant circuit (e.g. air)
1. Air intake temperature of indoor unit too high.