Control System, Functional Description; Start Mode; Normal Operation Mode; Modulating Mode - Sullair LS-12 Operators Manual And Parts Lists

Industrial air compressor. 40, 50, 60, 75 & 100hp (30, 37, 45, 55 & 75kw) standard & 24 kt
Hide thumbs Also See for LS-12:
Table of Contents

Advertisement

er and is directed towards the bottom of the sepa-
rator element. The direction of movement is
changed and its velocity significantly reduced, thus
causing large droplets of fluid to separate and fall to
the bottom of the receiver/sump. The fractional per-
centage of fluid remaining in the compressed air
collects on the surface of the separator element as
the compressed air flows through the separator.
Return lines (or scavenge tubes) lead from the bot-
tom of the separators' elements to the inlet region
of the compressor unit. Fluid collecting on the bot-
tom of the separator is returned to the compressor
by a pressure differential between the receiver and
the compressor inlet. Visual sight glasses are lo-
cated on the return lines to observe the fluid flow.
There are also orifices in the return line (protected
by strainers) to assure proper flow. A gauge, lo-
cated on the instrument panel, shows red if abnor-
mal pressure drop through the separators devel-
ops. At this time, separator element replacement is
necessary.
The receiver is ASME code rated at 175 psig (12.1
bar) working pressure. A minimum pressure/check
valve, located downstream from the separator, as-
sures a minimum receiver pressure of 55 psig (3.8
bar) during all conditions. This pressure is neces-
sary for proper air/fluid separation and proper fluid
circulation.
A terminal check valve is incorporated into the mini-
mum pressure/check valve to prevent compressed
air in the service line form bleeding back into the re-
ceiver on shutdown and during operation of the
compressor in an unloaded condition.
A pressure relief valve (located on the wet side of
the separator) is set to open if the sump pressure
exceeds 175 psig (12.1 bar). A temperature switch
will shut down the compressor if the discharge tem-
perature reaches 235_F (113_C).
All compressor models are equipped with a high
pressure shutdown switch to shut down the com-
pressor at 135 psig (9.3 bar). This prevents the
pressure relief valve from opening under routine
conditions, thereby preventing fluid loss through
the pressure relief valve.
WARNING
!
DO NOT remove caps, plugs, and/or other com-
ponents when compressor is running or pressur-
ized.
Stop compressor and relieve all internal pres-
sure before doing so.
Fluid is added to the sump via a capped fluid filler
opening, placed low on the tank to prevent overfil-
ling of the sump. A sight glass enables the operator
to visually monitor the sump fluid level.
2.6 CONTROL SYSTEM,
SCRIPTION
Refer to Figure 2---5. The purpose of the compres-
sor control system is to regulate the compressor air
intake to match the amount of compressed air be-
ing used. The control system consists of a Sulli-
con control, a butterfly valve (located on the com-
pressor air inlet), a pressure switch, a solenoid
valve and pressure regulator. The functional de-
scription of the control system is described below
in four distinct phases of compressor opera-
tion.The following descriptive text applies to all 12
and 16 Series compressors. For explanatory pur-
pose this description will apply to a compressor
with an operating pressure range of 100 to 110
psig (6.9 to 7.6 bar). A compressor with any other
pressure range would operate in the same manner
except for the stated pressures.
START MODE --- 0 TO 55 PSIG (0 TO 3.8 BAR)
When the compressor START button is depressed,
the sump pressure will quickly rise from 0 to 55 psig
(0 to 3.8 bar). During this period both the pressure
regulator and the solenoid valve are closed and the
Sullicon Control is inoperative. The spring on the
control holds the butterfly valve fully open and the
compressor pumps at full rated capacity. The rising
compressed air pressure is isolated from the ser-
vice line in this phase by the minimum pressure
valve, set approximately at 55 psig (3.8 bar).
NORMAL OPERATION MODE --- 55 TO 100 PSIG
(3.8 TO 6.9 BAR)
When the compressor air pressure rises above 55
psig (3.8 bar), the minimum pressure valve opens
and delivers compressed air to the service line.
From this point on, the line air pressure is continual-
ly monitored by a line pressure gauge. The pres-
sure regulator and the solenoid valve remain
closed during this phase, keeping the Sullicon
Control inactive.
MODULATING MODE --- 100 TO 110 PSIG (6.9
TO 7.6 BAR)
If less than the rated capacity of compressed air is
being used, the service line pressure will rise above
100 psig (6.9 bar). The pressure regulator valve
gradually opens, applying air pressure to the dia-
phragm chamber of the Sullicon Control which par-
tially closes the butterfly valve on the compressor
air inlet, reducing the amount of air entering the
compressor until it matches the amount of air being
used. The control system functions continually in
this manner, between the limits of 100 to 110 psig
(6.9 to 7.6 bar), in response to varying demands
from the service line.
The pressure regulator has an orifice which vents a
small amount of air to the atmosphere when the
pressure regulator controls the butterfly valve. The
orifice also bleeds any accumulated moisture from
the Sullicon Control.
Section 2
DESCRIPTION
FUNCTIONAL
DE-
9

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ls-16

Table of Contents