Install Chassis into Rack or Cabinet

Ensure that there is adequate clearance surrounding the rack or within the
cabinet to permit access and airflow.
Step
Task
Dell Force10 recommends that one person hold the chassis in place
1
while a second person attaches the brackets to the posts.
Attach the bracket "ears" to the rack or cabinet posts, using two screws
2
for each bracket. Ensure the screws are tightened firmly.
S55
S60
PSU0

Attach a Ground Cable to the System

The system is shipped with necessary 10-32 screw(s) for attaching a ground
cable to the chassis. The cable itself is not included. Dell Force10 recommends a
6AWG one-hole (for the S55) or two-hole (for the S60) lug, #10 hole size, 63"
spacing (not included in shipping) to properly ground the chassis. The lug must
be a UL recognized, crimp-type lug.
NOTE: The rack installation ears are not suitable for grounding.
CAUTION: Grounding conductors must be made of copper. Do not use
aluminum conductors.
PSU0
PSU1
PSU1
Rack Mounting
Rack/Cabinet
"ears"
Post
Rack/Cabinet
Post
Rack Mounting
ears
Installing the Hardware