NOTE: Coat the one-hole lug with an anti-oxidant compound prior to crimping.
Bring any un-plated mating surfaces to a shiny finish, and coat with an anti-oxidant
prior to mating. Plated mating surfaces must be clean and free from contamination.
Step
Task
Take the 10-32 screw(s) from the package.
1
Cut cable to desired length. Cable length must facilitate the proper
2
operation of fault interrupt circuits. Dell Force10 recommends using of
the shortest cable route allowable.
Attach the lug to the chassis as shown, using the supplied 10-32
3
screw(s) with captive internal tooth lock washer. Each screw should be
torqued to 20 in-lbs.
S55
S60
1
2
Attach the other end of the ground cable to a suitable ground point. The
4
rack installation ears are not a suitable grounding point.
The S60 is shipped with 2 10-32 screws for attaching a ground cable to the
chassis. The cable itself is not included. Dell Force10 recommends a 6AWG
two-hole lug, #10 hole size, 63" spacing (not included in shipping) to properly
ground the chassis. The two-hole lug must be a UL recognized, crimp-type lug.
8
Installing the Hardware