Appendix A: Communications; Modbus Address Table - Siemens 9200 Features Manual

Power meter
Hide thumbs Also See for 9200:
Table of Contents

Advertisement

Appendix A: Communications

This section describes the Modbus communications protocol employed
by a meter with the Megawatt option in a Modbus network. It is assumed
that the user is familiar with serial communications in general, and the
Modbus protocol. Refer to the document 9200 Modbus Protocol for more
information.

Modbus Address Table

In the following Modbus map, many numeric measurements are scaled.
Scaling is either fixed or programmable.
For an example of fixed scaling, suppose that the frequency register 40115
contains the value 5987. Since this register is scaled by "x100" the actual
measured value is 59.87 Hz.
For an example of programmable scaling, suppose that the meter Vln a
value is 480.1. If the PVS scaling is set to "x10" (default), then register 40100
will contain a value of 4801. If the PVS scaling is set to "0.1," then register
40100 will contain a value of 48. The meter supports programmable
scaling for voltage (PVS), current (PCS), neutral current (PnS), and power
(PPS).
Modbus Addr
Meter Measurement
40001
manufacturer's ID
40003
firmware revision
40004
oem ID
40005
meter options
40007
# meter power ups
# peak demand
40008
resets
40009
meter on-time
40011
# flash erase cycles
40013
device type
40014
Reserved
demand interval
40015
down counter
Reserved
40100
kVln a
40101
kVln b
Format
Scale
UINT32
x1
UINT16
x1
UINT16
x1
UINT32
x1
UINT16
x1
UINT16
x1
UINT32
x1
UINT32
x1
UINT16
x1
UINT16
x1
UINT16
PVS
UINT16
PVS
Appendix A: Communications
Default Scale
Description
See note 1.
See note 2.
See note 3.
See note 4.
See note 5.
x10
See note 6.
x10
13