PERIODIC TESTING RECOMMENDED CHECK LIST

ITEM
Atomizing Air/Steam
High and Low Gas
Pressure Interlocks
High and Low Oil
Pressure Interlocks
High and Low Oil
Temperature Interlocks
Fuel Valve Interlock
Switch
Purge Switch
Burner Position Interlock
Low Fire Start Interlock
Automatic Changeover
Control (dual fuel)
Safety Valves
Inspect Burner Components Semi-annually
Boiler Hydro-Test
FREQUENCY
ACCOMPLISHED BY
Annually
Service Technician
Monthly
Operator
Monthly
Operator
Monthly
Operator
Annually
Service Technician
Annually
Service Technician
Annually
Service Technician
Annually
Service Technician
At Least Annually
Service Technician
As required
Operator
Service Technician
Annually
Service Technician
REMARKS
Refer to burner instructions
Refer to burner instructions
Refer to burner instructions
Refer to burner instructions
Refer to burner instruction
Refer to burner instructions
Refer to burner instructions
Refer to burner instructions
Under supervision of gas utility
In accordance with procedure in
Section VI, ASME Boiler and
Pressure Vessel Code,
Recommended Rules for Care
and Operation of Heating
Boilers or Section VII for power
boilers.
Refer to burner instructions
Performed as required, in
accordance with NBIC Part 2,
not to exceed 90% of relief
valve setting.
25