Recommended Boiler Piping For Zoning With Valves - Burnham LEDV SERIES Installation & Service Instructions Manual

Ledv series direct vent oil fired boiler
Table of Contents

Advertisement

D
. Install Drain Valve in return piping. See figure 5.
E.
Oil, grease, and other foreign materials which
accumulate in new hot water boilers and a new or
reworked system should be boiled out, and then
thoroughly flushed. A qualified water treatment
chemical specialist should be consulted for
recommendations regarding appropriate chemical
compounds and concentrations which are compatible
with local environmental regulations.
F
. After the boiler and system have been cleaned and
flushed, and before refilling the entire system add
appropriate water treatment chemicals, if necessary, to
bring the pH between 7 and 11.
G.
Fill entire heating system with water and vent air
from system. Use the following procedure on a Series
Loop System equipped with zone valves. (See Figure
5).
1. Close isolation valve in boiler supply piping.
2. Isolate all circuits by closing zone valves or
balancing valves.
3. Attach a hose to bib cock located just below
Figure 5: Recommended Boiler Piping for Zoning with Valves
isolation valve in boiler supply piping. (Note -
Terminate hose in five gallon bucket at a suitable
floor drain or outdoor area).
4. Starting with one circuit, open zone valve.
5. Open bib cock.
6. Open fill valve (Make-up water line should be
located directly above isolation valve in boiler
supply piping).
7. Allow water to overflow from bucket until dis charge
from hose is bubble free for 30 seconds.
8. Open zone valve to the second zone to be purged,
then close the first. Repeat this step until all zones
have been purged, but always have one zone open.
At completion, open all zone valves.
9. Close bib cock, continue filling the system until
the pressure gauge reads 12 psi. Close fill valve.
(Note - If make-up water line is equipped with
pressure reducing valve, system will automatically
fill to 12 psi.
10. Open isolation valve in boiler supply piping.
11. Remove hose from bib cock.