SecTiON iii – iNSTALLATiON iNSTRUcTiONS (continued)
RECOMMENDED PIPING TO
BUILT-IN TANKLESS HEATERS
must be mounted so that cut off point is above
marking on Lowest Permissible Water Line Plate.
f. I nstall Pressure Safety Relief Valve, using fittings
furnished, into 1-1/2" pipe tapping in upper corner
of End Section. DO NOT INSTALL A SHUTOFF
VALVE BETWEEN SAFETY RELIEF VALVE
AND BOILER. Safety Relief Valve must be
installed in a Vertical Position with handle up.
g. Install Boiler Drain Valve into one of unused return
tappings that has been bushed to ¾". Drain Valve
can also be installed in return piping, preferably
in leg of tee that is located in line with return
connection on Boiler.
35.
CONNECT PIPING TO BUILT-IN HEATER(S) IF
USED, see Fig. 30, top - left side of this page.
FIG. 30
TABLe i - NATURAL GAS
Maximum Capacity of Piping in Cubic Feet of Gas Per Hour
(Based on a Pressure Drop of 0.3" Water
and 0.6 Specific Gravity)
Pipe
NOMINAL IRON PIPE SIZE IPS INCHES
Length
¾
1
in Feet
10
278
520
1050
20
190
350
730
30
152
285
590
40
130
245
500
50
115
215
440
60
105
195
400
70
96
180
370
80
90
170
350
90
84
160
320
100
79
150
305
125
72
130
275
150
64
12
250
175
59
110
225
200
55
100
210
TABLe ii
Multipliers to be used with Table I when Pressure Drop is not 0.3"
Pressure Drop
0.1
0.2
0.5
1.0
0.3
TABLe iii
Multipliers to be used with Tables I and II for
Specific Gravity Other than 0.60
Specific Gravity
.50
.55
.60
.65
.70
36.
OPEN GAS TRAIN CARTON(S)
CONNECT GAS TRAIN(S) TO ELBOW ON END OF
MANIFOLD(S) according to the Gas Trains on pages
86, 87, 88, 89, 90, 91 or 92.
PRESSURE TESTING of gas service piping must be
done before connecting to the boiler gas train. Test for
leaks by introducing, from an isolated source, air or
inert gas to the piping. Piping shall withstand 3 PSI
gage pressure for a period of not less than 10 minutes
without showing any drop in pressure.
37.
A DRIP LEG SHOULD BE PROVIDED IN THE
VERTICAL DROP TO EACH GAS TRAIN, see
Fig. 1. An additional Manual Shut-off valve and
2
3
1600
3050
4800
8500
1100
2100
3300
5900
890
1650
2700
4700
760
1450
2300
4100
670
1270
2000
3600
610
1150
1850
3250
560
1050
1700
3000
530
990
1600
2800
490
930
1500
2600
460
870
1400
2500
410
78
1250
2200
380
710
1130
2000
350
650
1050
1850
320
610
980
1700
Multiplier
.577
.815
1.29
1.83
1.00
Correction Factors
1.10
1.04
1.00
.96
.93
4
17500
12000
9700
8300
7400
6800
6200
5800
5400
5100
4500
4100
3800
3500
31