Memory defect Memory error
SSC/ASC
EEPROM failure
defect
ADC defect
ADC failure
Communication
Either:
processor
1. PROFIBUS card not found.
defect
2. HART card not found.
DSP defect
DSP failure
Inaccurate
measurement
DSP failure
value
Software error Software watchdog time-out
One or more of:
1. Temperature calibration value
out of range.
Self-calibration
2. Analog output calibration
error
values not calibrated.
3. 'ReferenceLength' or
' A ntennaOffset' not calibrated
Invalid
Parameters are inconsistent
parameter
(for example, URV=LRV).
setting
Unit Repair and Excluded Liability
All changes and repairs must be done by qualified personnel and applicable safety
regulations must be followed. Please note the following:
The user is responsible for all changes and repairs made to the device.
All new components must be provided by Siemens Milltronics Process
Instruments Inc.
Restrict repair to faulty components only
Do not re-use faulty components.
Page 74
SITRANS LR 400 (Solids) – INSTRUCTION MANUAL
Possible causes
Electronics
Software
Application
Remedy
Reset power. If defect persists, perform a
factory reset. If still defective, contact your
local Siemens representative.
Repair required: contact your local Siemens
representative.
Repair required: contact your local Siemens
representative.
Repair required: contact your local Siemens
representative.
Repair required: contact your local Siemens
representative.
Repair required: contact your local Siemens
representative.
Repair required: contact your local Siemens
representative.
Repair required: contact your local Siemens
representative.
Adjust customer parameters.