ABB ACS800-07-0610-3 Hardware Manual page 9

Acs800-07 series 500 to 2800 kw
Table of Contents

Advertisement

CHANGED (page 115): LEDs
LED
V309 (red)
NEW (page 126): Ambient conditions
Cabinets with option +Q968: the installation site altitude in operation is 0 to 2000 m.
Installation site altitude
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Action
• Close the disconnector and switch the power on.
• Test the operation of the STO function when the
motor is stopped:
- Give a stop command for the drive (if running)
and wait until the motor shaft is at standstill.
- Activate the STO circuit and give a start
command for the drive.
- Ensure that the motor stays at standstill.
- Deactivate the STO circuit.
• Restart the drive and check that the motor runs
normally.
• Test the operation of the STO function when the
motor is running:
- Start the drive and ensure that the motor is
running.
- Activate the STO circuit.
- Ensure that the motor stops and the drive trips.
- Reset the fault and try to start the drive.
- Ensure that the motor stays at standstill.
- Deactivate the STO circuit.
• Restart the drive and check that the motor runs
normally.
Indication
Prevention of unexpected start (option +Q950) or Safe torque off (option +Q968) is
ON.
installed for stationary use
[...]
Cabinets with option +Q968:
0 to 2000 m
Additional information
Operation
5
Update Notice