126
Cooling
Method
Filter material
Free space around the unit
Cooling air flow
Degrees of protection
Ambient conditions
Installation site altitude
Air temperature
Relative humidity
Contamination levels
(IEC 60721-3-3, IEC 60721-3-
2, IEC 60721-3-1)
Atmospheric pressure
Vibration (IEC 60068-2)
Shock (IEC 60068-2-29)
Free fall
Technical data
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Internal fans, flow direction from bottom to top
IP22/IP42 units Luftfilter airTex G150
IP54 units Luftfilter airComp 300-50
See chapter
Mechanical
installation.
See
Ratings.
IP21; IP22; IP42; IP54, IP54R (with air outlet duct)
Environmental limits for the drive are given below. The drive must be used in a heated,
indoor controlled environment.
Operation
installed for stationary use
0 to 4000 m (13123 ft) above
sea level [above 1000 m
(3281 ft), see section
Derating]
-15 to +50 °C (5 to 122 °F),
no frost allowed. See section
Derating.
5 to 95%
No condensation allowed. Maximum allowed relative humidity is 60% in the presence of
corrosive gases.
No conductive dust allowed.
Boards without coating:
Chemical gases: Class 3C1
Solid particles: Class 3S2
Boards with coating:
Chemical gases: Class 3C2
Solid particles: Class 3S2
70 to 106 kPa
0.7 to 1.05 atmospheres
Max. 1 mm (0.04 in.)
(5 to 13.2 Hz),
2
2
max. 7 m/s
(23 ft/s
)
(13.2 to 100 Hz) sinusoidal
Not allowed
Not allowed
Inlet (door)
Storage
in the protective package
-
-40 to +70 °C (-40 to +158°F) -40 to +70 °C (-40 to +158°F)
Max. 95%
Boards without coating:
Chemical gases: Class 1C2
Solid particles: Class 1S3
Boards with coating:
Chemical gases: Class 1C2
Solid particles: Class 1S3
70 to 106 kPa
0.7 to 1.05 atmospheres
Max. 1 mm (0.04 in.)
(5 to 13.2 Hz),
2
2
max. 7 m/s
(23 ft/s
)
(13.2 to 100 Hz) sinusoidal
2
2
Max. 100 m/s
(330 ft./s
),
11 ms
100 mm (4 in.) for weight
over 100 kg (220 lb)
Outlet (roof)
–
Luftfilter airTex G150
Transportation
in the protective package
-
Max. 95%
Boards without coating:
Chemical gases: Class 2C2
Solid particles: Class 2S2
Boards with coating:
Chemical gases: Class 2C2
Solid particles: Class 2S2
60 to 106 kPa
0.6 to 1.05 atmospheres
Max. 3.5 mm (0.14 in.)
(2 to 9 Hz),
2
2
max. 15 m/s
(49 ft/s
)
(9 to 200 Hz) sinusoidal
2
2
Max. 100 m/s
(330 ft./s
),
11 ms
100 mm (4 in.) for weight
over 100 kg (220 lb)