CASTILE FREESTANDING
I. Pellet Venting Charts
The maximum horizontal venting allowed with no vertical vent-
ing attached is 48 inches (1219mm) including one 90° elbow
or two 45° elbows. This is our recommended horizontal vent-
ing installation. Addition of any horizontal venting beyond 48
inches (1219mm) Hearth & Home Technologies strong recom-
mends a minimum of 60 inches (1524mm) of additional ver-
tical vent. Horizontal sections of vent pipe should have a 1/4
inch (6.35mm) rise per foot.
Hearth & Home Technologies recommends any installation
requiring more than two 90° elbows, or more than 15 feet
(4.5m) of venting to use 4 inch (102mm) vent.
ONE 90º ELBOW
Total
Minimum
Vent
Horizontal
Vertical
Diameter
4
0
3
5
5
3
6
6
3
7
7
3
8
8
4
9
9
4
10
10
4
11
11
4
12
12
4
13
13
4
14
14
4
15
15
4
16
16
4
17
17
4
18
18
4
19
19
4
see fig. 14.1
THREE 90º ELBOWS
Total
Horizontal Vertical
2
3
4
5
6
7
8
9
10
11
see fig. 14.3
NOTICE: These are guidelines for successful venting of your pellet appliance. The more vertical rise you can obtain in
your system, the better it will perform. Horizontal vent runs can accumulate ash and will need to be cleaned more often.
Try to keep them as short as possible.
14
TWO 90º ELBOWS
Total
Minimum
Horizontal
Vertical
2
5
3
6
4
7
5
8
6
9
7
10
8
11
9
12
10
13
11
14
12
15
13
16
14
17
15
18
see fig. 14.2
Minimum
Vent
Diameter
11
4
12
4
13
4
14
4
15
4
16
4
17
4
18
4
19
4
20
4
Fire Risk.
• Only LISTED venting components may be used.
• NO OTHER vent components may be used.
Substitute or damaged vent components may impair
safe operation.
45° elbow is equivalent to 1 foot (30.48cm) of straight pipe
90° elbow is equivalent to 3 feet (91.44cm) of straight pipe
Minimum Vertical Vent for One Elbow
Minimum Vertical Vent for One Elbow
Vent
20
Diameter
15
3
10
3
3
5
3
0
3
0
4
4
4
Figure 14.1
4
Minimum Vertical Vent for Two Elbows
4
Minimum Vertical Vent for Two Elbows
4
20
4
4
15
4
10
5
0
0
Figure 14.2
Minimum Vertical Vent for Three Elbows
Minimum Vertical Vent for Three Elbows
25
20
15
10
5
0
0
Figure 14.3
7021-154J
WARNING
5
10
15
Horizontal Run, (ft)
5
10
Length of Horizontal Sections, (ft)
2
4
6
8
Length of Horizontal Sections (ft)
20
15
10
12
May 12, 2017

Advertisement

Table of Contents
loading

This manual is also suitable for:

Castile-csb-bCastile-cwl-bCastile-pmh-b

Table of Contents