Instructing The Owner; Maintenance - York H2DH024S06 Installation Instruction

Condensing units split-system cooling 2 to 5 tons
Table of Contents

Advertisement

A "higher" than normal liquid pressure may point out a dirty
condenser coil, or non-condensibles in the system (not evacu-
ated properly) or a condenser fan motor not running at full
speed.
A "lower" than normal liquid pressure may point out an ineffi-
cient compressor (low head - high suction) or a low refrigerant
charge.
Check flare caps on Schrader fittings to be sure they are tight.
DO NOT OVERTIGHTEN (40-60 inch-lbs. maximum).
2 SPEED FAN OPERATION
CAUTION: 2 - 2.5 TON UNITS
Opens @ 70 ° F (drops to 850 RPM)
Closes @ 80 ° F (increases to 1075 RPM)
CAUTION: 3- 5 TON UNITS
Opens @ 70 ° F (drops to 575 RPM)
Closes @ 80 ° F (increases to 850 RPM)

INSTRUCTING THE OWNER

Assist owner with processing warranty cards. Review Owners
Guide and provide a copy for the owner guidance on proper
operation and maintenance. Instruct the owner or the operator
how to start, stop and adjust temperature setting.
When applicable, instruct the owner that the compressor is
equipped with a crankcase heater to prevent the migration of
refrigerant to the compressor during the "OFF" cycle. The
heater is energized only when the unit is not running. If the main
switch is disconnected for long periods of shut down, do not
attempt to start the unit 8 hours after the switch has been
connected. This will allow sufficient time for all liquid refrigerant
to be driven out of the compressor.
The installer should also instruct the owner on proper opera-
tion and maintenance of all other system components.
INDICATIONS OF PROPER OPERATION
Cooling operation is the same as any conventional air condi-
tioning unit.
The following checks may be made to determine if the system
is operating properly:
1. The outdoor fan should be running, with warm air being
discharged from the top of the unit.
Unitary Products Group
2. The indoor blower (furnace or air handler) will be operating,
discharging cool air from the ducts.
3. The vapor line at the outdoor unit will feel cool to the touch.
4. The liquid line at the outdoor unit will feel warm to the touch.
NOTICE TO OWNER
If unit is not operating properly, check the following items before
calling a serviceman:
1. Indoor section for dirty filter.
2. Outdoor section for leaf or debris blockage.
Eliminate problem, turn off the thermostat for 10 seconds and
attempt start. Wait 5 minutes. If system does not start, call
serviceman.

MAINTENANCE

1. Dirt should not be allowed to accumulate on the outdoor
coils or other parts in the air circuit. Clean as often as
necessary to keep the unit clean. Use a brush, vacuum
cleaner attachment, or other suitable means.
2. The outdoor fan motor is permanently lubricated and does
not require periodic oiling.
3. If the coil needs to be cleaned, it should be washed with
Calgon Coil Clean (mix one part Coil Clean to seven parts
water). Allow solution to remain on coil for 30 minutes
before rinsing with clean water. Solution should not be
permitted to come in contact with painted surfaces.
4. Refer to the furnace or air handler instructions for filter and
blower motor maintenance.
5. The evaporator coil drain pan should be inspected and
cleaned regularly to prevent odors and assure proper drain-
age.
CAUTION: IT IS UNLAWFUL TO KNOWINGLY VENT, RE-
LEASE OR DISCHARGE REFRIGERANT INTO THE OPEN
AIR DURING REPAIR, SERVICE, MAINTENANCE OR THE
FINAL DISPOSAL OF THIS UNIT.
WHEN THE SYSTEM IS FUNCTIONING PROPERLY AND
THE OWNER HAS BEEN FULLY INSTRUCTED, SECURE
THE OWNER'S APPROVAL.
550.36-N2Y
11

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

H2dh042s06H2dh030s06H2dh036s06H2dh048s06H2dh060s06

Table of Contents