Connection
3.1

Power connections

Incorrect connection to the mains will destroy the unit!
The excitation coils of contactors and relays connected to the same mains network as the
unit, or which are located in its proximity, must be wired with surge arresters, e.g. RC
networks.
The unit must not be operated via a current-operated earth-leakage circuit-breaker (DIN
VDE 0160).
A voltage may only be applied to the unit after connecting SIMOVERT Master Drives.
Swapping or shorting the dc link terminals will destroy the SIMOVERT Master Drives
inverter!
The units are intended for permanent connection to the mains in conformity with DIN VDE 0160 Section 6.5.2.1.
PE conductor connection: minimum cross-section 10mm
The units must be fused on the mains side with semiconductor fuses as
detailed in Table 3.2. To avoid retroactive effects on the mains and to limit
harmonics, the mains should be connected via a 2 % commutation choke as
detailed in Table 3.3. Mains plus commutation activity must be ≥ 3% u
load carrying capacity of the dc link capacitors in the inverter). See Table 3.2
for details of order numbers for fuses.
The connection cross-sections given in Table 3.1 were determined for copper
cables at 40 °C (104 °F) ambient temperature. Data applies to multiple-wire
cables.
The terminals accept the following range of cables:
2
Type B: 2,5mm
to 16mm
2
Type C: 10mm
to 50mm
Unit order No.
voltage
6SE70
24-1EB85-0AA0
200 to 480
28-6EC85-0AA0
200 to 480
24-1FB85-0AA0
500 to 600
27-2FC85-0AA0
500 to 600
28-8FC85-0AA0
500 to 600
Table 3.1
Mains connection
1) American Wire Gauge
3-2
ENGLISH
2
/ AWG 14 to AWG 6
2
/ AWG 8 to AWG 1/0
Rated
input-
U1/L1, V1/L2, W1/L3
current
(V)
(A)
mm
36
16
74
50
36
16
62
35
82
50
WARNING
2
.
(ac
k
Conductor
Conductor
C/L+, D/L-
2
1)
2
AWG
mm
6
16
1/0
50
6
16
2
35
1/0
50
Mains
dc link
W1
C
L3
V1
L+
L2
PE
U1
L1
X1
Figure 3.1 Mains connection
Conductor
PE
1)
2
AWG
mm
AWG
6
16
1/0
25
6
16
2
16
1/0
25
Siemens AG
6SE7087-6AC85-0AA0
Common Rectifier
Operating instructions