Sinamics Perfect Harmony Gh180 6Sr41 Manufactured In Nma Nuernberg, Germany - Siemens GH180 Operating Instructions Manual

Medium-voltage drive sinamics perfect harmony
Hide thumbs Also See for GH180:
Table of Contents

Advertisement

Technical Data
B.4 System Specifications
B.4
System Specifications
B.4.1
9 Cell System Specifications
Table B-4
9-Cell System Parameters
Cells in Drive
(without Redundancy)
9
9
9
Parameters
Input Line Voltage
Input Frequency
Input Power Factor
Input Harmonics
Efficiency
Output Voltage
Output HVF
Output dv/dt
Overload Capacity
Output Frequency & Drift
Output Torque
Design Life
Auxiliary Voltage
Enclosure Type
Degree of Protection
Ambient Temperature
Altitude
Sound level
Cooling
180
Output Voltage
Available L-L (with O-M)
4000 V (4160 V)
4000 V (4160 V)
4000 V (4160 V)
Ratings
2.4, 3.0, 3.3, 4.16, 4.8, 6.0, 6.3, 6.6, 6.9, 7.2, 8.4, 10, 11, 12, 12.47, 13.2, or 13.8 kV; 3 phase;
10% / -5%
50 or 60 Hz ±5%
> 0.95 above 10% load
<= 5% TDD with ambient THDv <= 2%
Copper Wound Transformer: 98% Transformer, 99% Converter, > 96,5% Total VFD
Aluminium Wound Transformer: 97.5% Transformer, 99% Converter, > 96% Total VFD
9 Cell
2300 V
3000 V
3300 V
4000 V
4160 V
< 0.03
< 3000 V/µS
110 % 1 minute / 10 minute
0.5 - 330 Hz, ± 0.5 % (derates at <10 Hz and at >167 Hz)
1
10 - 167 Hz rated torque (2 - Quadrant)
20 years
200 V, 380 V - 400 V - 415 V, 50 Hz;
230 V, 460 - 480 V, 575 V, 60 Hz; 3 phase
NEMA 1 Ventilated
IP21 (optional IP42)
0 - 40°C (maximum 50° C, derating starts from 40°C on)
0 - 3300 ft. without derating (maximum 12,300 ft with derating)
80 dB(A)
Ventilated, forced air-cooled with integrated fans

SINAMICS PERFECT HARMONY GH180 6SR41 manufactured in NMA Nuernberg, Germany

Hp Range
Power Cell Types
(Continuous Current Rating)
200-1100
40, 70, 100, 140
800-2250
40, 70, 100, 140, 200, 260
1500-3500
315, 375
2
Operating Instructions Rev.201706301306

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

6sr41