CORAYVAC
I
NSTALLATION

SECTION 5: HEATER INSTALLATION

To ensure your safety, and comply with the terms of
the warranty, all heaters must be installed in accor-
dance with these instructions.
The gas or the electrical supply lines must not be
used to support the heater.

Figure 8: Critical Hanger Placement

Description
Part Number
Turnbuckle
91903201
Bow Shackle
E0007576
Tube/Reflector Hanger
03090100
10
O
S
M
PERATION AND
ERVICE
WARNING
Crush Hazard
Hang heater with materials
with a minimum working
load of 33 kg (75 lbs).
Failure of the supports can
result in death, injury
or property damage.
"X"
(see table)
ANUAL
Do not locate the gas or electric supply lines directly
over the path of the flue products from the heater.
The heater must be installed in a location that it is
readily accessible for servicing.
The heater must be installed with clearances to
combustibles as indicated in this instruction manual.
The minimum and maximum gas inlet pressures
must be maintained as indicated in this manual.
Typical installation configurations are shown in
Figure 8.
For mounting height and tube lengths See Page 43,
Section 15.6.
Run Length
15m (50')
31m (100')
46m (150')
61m (200')
76m (250')
Typical Expansion
Minimum "X" Length
±25 mm (1")
300 mm (12")
±50 mm (2")
600 mm (24")
±75 mm (3")
900 mm (36")
±100 mm (4")
1200 mm (46")
±125 mm (5")
1450 mm (57")