Case 4: Cabling of the digital output contacts to monitor other filter operation modes
than warnings and alarms.
Case 5: Cabling of main/auxiliary control functionality.
Case 6: Implementation of local start/stop buttons.
WARNING: Before cabling any of the circuits discussed below, switch off the power
supply to the filter. When the filter has already been installed on site, this is done by
opening the protection system located just upstream of the filter and opening the
auxiliary fuse box present in the filter. Wait at least 25 minutes to allow for the DC
capacitors to discharge when the filter has been connected to the network before.
Failure to do so may result in the lethal injury or death.
After making and verification of all the electrical connections
-
Close the auxiliary fuse box of the filter units starting from the last slave and
ending with the master unit.
-
Reclose the filter unit(s).
The power to the filter may then be restored.
-

6.12.1 Cabling of remote control functionality

The PQFM has the possibility to be controlled by remote control. An example of this
approach is a drive that is switched on at a location and which automatically gives a start
command to the filter. When the drive is then stopped, the drive sends automatically a
stop command to the filter too. This section gives an example of how the cabling has to
be done on the filter side.
Any of the two digital inputs on the PQF-Manager (Cf.
the remote control functionality. The electrical requirements of the digital inputs are
given in
Table 67
(Filter characteristics section).
implement the remote control functionality on Digital Input 1.
Figure 59
Manual Power Quality Filter PQFM ç Electrical design and installation 75
Figure
57) can be used to cable
gives an example of how to