ABB PQFM Instruction Manual page 225

Power quality filter
Table of Contents

Advertisement

Line voltage imbalance
Surge withstand capability with
optional surge arrester
Insulation voltage (Ui)
Network voltage: 208 V £ Ue £ 480 V
(Voltage group V1)
Network voltage: 480 V £ Ue £ 690 V
(Voltage group V2)
Auxiliary circuit voltage (internally
derived)
Neutral connection systems
EMC-Environment class (according to
IEC 60439-1) (CE version only)
Compliance with standards
General construction aspects
EMC immunity (CE version only)
EMC emissions (CE version only)
Filter characteristics
RMS output current per power unit type (50Hz or 60Hz network).
Network voltage: 208 V £ Ue £ 480 V
(Voltage group V1)
Network voltage:
480 V < Ue £ 690 V (Voltage group V2),
CE version
480 V £ Ue £ 600 V (Voltage group V2),
cULus version
Modularity
Redundancy
S
: Transformer nominal power
trafo
z
:
Transformer impedance in %
trafo
z
:
Impedance between notch producing load
load
and filter connection point (% in load base)
Maximum 2% of phase to phase voltage
According to IEC1643-1
480V
690V for CE version
600V for cULus version
230 Vrms (+/- 10%)
Not applicable
2
EN-61439-1 (2011)
EN/IEC 61000-6-2, Industrial level
EN/IEC 61000-6-4, Class A
Unit type 1 (M07, S07): 70 A
Unit type 2 (M10, S10): 100 A
Unit type 3 (M13, S13): 130 A
Unit type 4 (M15, S15): 150 A
Unit type 1 (M10, S10): 100 A
Up to 8 power units/filter (possible to use different power
unit ratings of the same voltage group but difference
between smallest and biggest unit should maximum be
one current category.)
The units (master, slave) must have PQF-Manager
firmware version 2.11.ro or higher.
One power unit per cubicle.
For full redundancy combine master units of same rating.
If any unit in a master-master filter system fails, the other
units can keep running.
Manual Power Quality Filter PQFM ç Technical specifications 225