(Voltage group V1)
Unit rating: 100 A
Network voltage: 208 V £ Ue £ 480 V
(Voltage group V1)
Unit rating: 130 A
Network voltage: 208 V £ Ue £ 480 V
(Voltage group V1)
Unit rating: 150 A
Network voltage:
480 V £ Ue £ 690 V, CE version
480 V £ Ue £ 600 V, cULus version
(Voltage group V2)
Unit rating: 100 A
Phase to earth resistance
Noise intensity
Communication
Programming
Fuse information
Main circuit fuses (CE version optional):
Vsupply: 208V £ Ue £ 480V
Vsupply: 480V £ Ue £ 690V
Main circuit fuses (cULus version):
Vsupply: 208V £ Ue £ 480V
Vsupply: 480V < Ue £ 600V
Auxiliary circuit fuses (CE version):
Vsupply: 208V £ Ue £ 480V
Vsupply: 480V £ Ue £ 690V
Auxiliary circuit fuses (cULus version):
Vsupply: 208V £ Ue £ 480V
Vsupply: 480V < Ue £ 600V
Surge arrester fuses (CE version only,
optional)
Main options
2.7 kW
4.2 kW
2.8 kW
1.67 MW/filter unit
69.6 dBA typically
Through PQF-Manager display.
Through Modbus RTU (with optional RS485 Modbus
Adapter).
Through Modbus TCP (with Ethernet).
Through dedicated optional software PQ-link (with USB-
Ethernet).
Through PQF-Manager display.
Through USB-Ethernet with dedicated optional software
(PQ-Link).
70-100A: NH Fuse gL or gG, 160A, 500V, Isc 120kA
130-150A: NH Fuse gL or gG, 200A, 500V, Isc 120kA
100A: NH Fuse gL or gG, 125A, 690V, Isc 80kA
Class J Time delay, 175A, 600V, Isc 200kA
Class J Time delay, 175A, 600V, Isc 200kA
French Ferrule 10 x 38 gG/gl, 6A, 500V, Isc ~120kA
French Ferrule 14 x 51 gG/gl, 6A, 690V, Isc ~ 80kA
Class CC, 6A, 600V, Isc 200kA
Class CC, 6A, 600V, Isc 200kA
size 0, 125A, gG/gL, with striker
Manual Power Quality Filter PQFM ç Technical specifications 227
£ 3.5 kW
£ 5.0 kW
£ 3.6 kW