Blower Data - Lennox LGH180H Installation Instructions Manual

13 ton, 15 ton, 17.5 ton, 20 ton, 25 ton rooftop packaged units
Hide thumbs Also See for LGH180H:
Table of Contents

Advertisement

BLOWER DATA

FACTORY INSTALLED BELT DRIVE KIT SPECIFICATIONS
Motor Efficiency
Standard or High
Standard or High
Standard
Standard
High
High
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
Standard
NOTE - Using total air volume and system static pressure requirements determine from blower performance tables rpm and motor output required. Maximum usable
output of motors furnished are shown. In Canada, nominal motor output is also maximum usable motor output. If motors of comparable output are used, be sure to keep
within the service factor limitations outlined on the motor nameplate.
NOTE – Units equipped with an inverter are limited to a motor service factor of 1.0.
FACTORY INSTALLED OPTIONS/FIELD INSTALLED ACCESSORY AIR RESISTANCE
Wet Indoor Coil
Air
Vol-
180U, 240U,
156H,
ume
210H, 240H,
180H
300S
CFM
in. w.g.
in. w.g.
2750
.01
.02
3000
.01
.02
3250
.01
.03
3500
.01
.03
3750
.01
.03
4000
.02
.04
4250
.02
.04
4500
.02
.05
4750
.02
.05
5000
.02
.05
5250
.02
.06
5500
.02
.07
5750
.03
.07
6000
.03
.08
6250
.03
.08
6500
.03
.09
6750
.04
.10
7000
.04
.10
7250
.04
.11
7500
.05
.12
8000
.05
.13
8500
.06
.15
9000
.07
.16
9500
.08
.18
10,000
.08
.20
10,500
.09
.22
11,000
.11
.24
Nominal hp
Maximum hp
2
2
3
3
3
3
5
5
5
7.5
7.5
7.5
10
10
10
Gas Heat Exchanger
Cond-
enser
Low/
Reheat
Medium
Standard
Coil
Heat
Heat
in. w.g.
in. w.g.
in. w.g. in. w.g. in. w.g.
.01
.02
.04
.01
.03
.04
.01
.03
.05
.02
.03
.05
.02
.04
.06
.02
.04
.06
.02
.04
.06
.02
.05
.07
.02
.05
.08
.02
.05
.09
.03
.06
.10
.03
.06
.10
.03
.06
.11
.03
.07
.12
.03
.07
.12
.04
.08
.13
.04
.08
.14
.04
.09
.15
.04
.09
.16
.05
.10
.17
.05
.11
.19
.05
.12
.20
.06
.13
.23
.07
.14
.25
.07
.16
.27
.08
.17
.30
.08
.18
.31
Page 18
Drive Kit Number
2.30
2.30
3.45
3.45
3.45
3.45
5.75
5.75
5.75
8.63
8.63
8.63
11.50
11.50
11.50
Econo
Electric
Heat
High
mizer
Heat
in. w.g. MERV 8 MERV 13 in. w.g. in. w.g.
.05
- - -
- - -
.05
- - -
- - -
.06
- - -
- - -
.06
- - -
- - -
.07
- - -
- - -
.07
- - -
- - -
.08
- - -
- - -
.09
- - -
- - -
.10
- - -
- - -
.11
- - -
- - -
.12
- - -
- - -
.13
- - -
- - -
.14
- - -
- - -
.15
.01
- - -
.16
.01
.01
.17
.01
.02
.18
.01
.03
.19
.01
.04
.20
.01
.05
.21
.01
.06
.24
.02
.09
.26
.02
.11
.29
.04
.14
.32
.05
.16
.35
.06
.19
.38
.09
.22
.40
.11
.25
RPM Range
1
535 - 725
2
710 - 965
1
535 - 725
2
710 - 965
3
685 - 856
4
850 - 1045
3
685 - 856
4
850 - 1045
5
945 - 1185
6
850 - 1045
7
945 - 1185
8
1045 - 1285
7
945 - 1185
10
1045 - 1285
11
1135 - 1365
Horizontal
Roof Curb
Filters
156
thru
240
.01
.03
- - -
.01
.03
- - -
.01
.04
.01
.01
.04
.01
.01
.04
.01
.04
.06
.06
.04
.06
.07
.04
.07
.07
.04
.07
.08
.05
.07
.08
.05
.07
.09
.05
.07
.10
.05
.08
.11
.05
.08
.11
.05
.08
.12
.05
.08
.13
.05
.08
.14
.06
.08
.15
.06
.09
.16
.06
.09
.17
.06
.09
.19
.06
.09
.21
.07
.10
.24
.07
.10
.26
.07
.11
.29
.07
.11
.31
.08
.11
.34
300S
- - -
- - -
- - -
- - -
- - -
- - -
- - -
.02
.03
.03
.04
.04
.05
.06
.07
.08
.08
.09
.10
.11
.13
.15
.17
.19
.21
.24
.27

Hide quick links: