Refrigerant Charge And Check - All-Aluminum Coils; Normal Operating Pressures - Lennox LGH180H Installation Instructions Manual

13 ton, 15 ton, 17.5 ton, 20 ton, 25 ton rooftop packaged units
Hide thumbs Also See for LGH180H:
Table of Contents

Advertisement

D-Refrigerant Charge and Check - All-Aluminum Coils
WARNING-Do not exceed nameplate charge under
any condition.
This unit is factory charged and should require no further
adjustment. If the system requires additional refrigerant,
reclaim the charge, evacuate the system, and add
required nameplate charge.
NOTE - System charging is not recommended below
60_F (15_C). In temperatures below 60_F (15_C), the
charge must be weighed into the system.
If weighing facilities are not available, or to check the
charge, use the following procedure:
IMPORTANT - Charge unit in standard cooling mode.
1- Make sure outdoor coil is clean. Attach gauge
manifolds and operate unit at full CFM in cooling mode
with economizer disabled until system stabilizes
(approximately five minutes). Make sure all outdoor air
dampers are closed.
2- Check each system separately with all stages
operating. Compare the normal operating pressures
(see tables 4 - 8) to the pressures obtained from the
gauges. Check unit components if there are
significant differences.
3- Measure the outdoor ambient temperature and the
suction pressure. Refer to the appropriate circuit
LGH/LCH156H NORMAL OPERATING PRESSURES - ALUMINUM COIL
65 °F
Suct
Disc
(psig)
(psig)
110
241
118
245
Circuit 1
137
255
154
266
111
249
119
253
Circuit 2
137
263
153
276
115
256
123
261
Circuit 3
140
273
157
284
TABLE 4

Normal Operating Pressures

Outdoor Coil Entering Air Temperature
75 °F
85 °F
Suct
Disc
Suct
(psig)
(psig)
(psig)
112
279
115
121
282
124
140
292
142
160
304
163
112
287
113
120
291
122
139
301
142
158
313
162
116
294
118
125
299
128
143
311
146
162
324
166
charging curve on Page 26 through Page 35 to
determine a target liquid temperature.
Note - Pressures are listed for sea level applications.
4- Use the same thermometer to accurately measure the
liquid temperature (in the outdoor section).
D If measured liquid temperature is higher than
the target liquid temperature, add refrigerant to
the system.
D If measured liquid temperature is lower than
the target liquid temperature, recover some
refrigerant from the system.
5- Add or remove charge in increments. Allow the system
to stabilize each time refrigerant is added or removed.
6- Continue
the
temperature
temperature. Do not go below the target liquid
temperature when adjusting charge. Note that
suction pressure can change as charge is adjusted.
7- Example LGH/LCH180H Circuit 1: At 95°F outdoor
ambient and a measured suction pressure of
130psig, the target liquid temperature is 96.5°F. For
a measured liquid temperature of 106°F, add charge
in increments until measured liquid temperature
agrees with the target liquid temperature.
95 °F
Disc
Suct
Disc
(psig)
(psig)
(psig)
321
117
367
324
127
370
333
145
378
346
163
392
328
116
374
332
124
378
342
145
387
356
164
402
335
120
381
340
130
386
353
149
398
367
169
413
Page 23
process
until
measured
agrees
with
the
target
105 °F
Suct
Disc
Suct
(psig)
(psig)
(psig)
119
419
122
129
420
131
148
431
152
171
441
174
118
423
121
127
428
129
146
438
149
167
451
171
122
429
124
132
436
133
152
449
154
171
462
174
507124-04
liquid
liquid
115 °F
Disc
(psig)
472
474
484
496
474
481
490
505
480
488
502
515
3/2016

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents