E-Refrigerant Charge and Check - Fin/Tube Coil
WARNING-Do not exceed nameplate charge under any condition.
This unit is factory charged and should require no further
adjustment. If the system requires additional refrigerant,
reclaim the charge, evacuate the system and add
required nameplate charge.
NOTE - System charging is not recommended below
60°F (15°C). In temperatures below 60°F (15°C), the
charge must be weighed into the system.
If weighing facilities are not available, or to check the
charge, use the following procedure:
IMPORTANT - Charge unit in normal cooling mode.
1- Attach gauge manifolds and operate unit in cooling
mode with economizer disabled until system
stabilizes (approximately five minutes). Make sure all
outdoor air dampers are closed.
2- Check each system separately with all stages
operating.
3- Use a thermometer to accurately measure the
outdoor ambient temperature.
4- Apply the outdoor temperature to tables 9 through 20
to determine normal operating pressures.
are listed for sea level applications at 80°F dry bulb and
67°F wet bulb return air.
5- Compare the normal operating pressures to the
pressures obtained from the gauges. Minor
variations in these pressures may be expected due to
differences in installations. Significant differences
could mean that the system is not properly charged
or that a problem exists with some component in the
system. Correct any system problems before
proceeding.
6- If discharge pressure is high, remove refrigerant from
the system. If discharge pressure is low, add
refrigerant to the system.
S Add or remove charge in increments.
S Allow the system to stabilize each time
refrigerant is added or removed.
7- Use the following approach method along with the
normal operating pressures to confirm readings.
TABLE 9
LG/LC Series 156H Std.
Circuit 1
Outdoor
Dis.
Suc.
Coil En­
+10
+5
tering
psig
psig
Air Temp
65_F
255
136
75_F
292
139
85_F
333
141
95_F
378
144
105_F
431
148
115_F
484
150
LGH/LCH156, 180, 210, 240, 300S
Pressures
Circuit 2
Circuit 3
Dis.
Suc.
Dis.
Suc.
+10
+5
+10
+5
psig
psig
psig
psig
263
136
273
140
301
139
311
144
342
141
353
146
387
143
398
148
438
145
449
150
490
146
502
152
LG/LC Series 156H Reheat
Circuit 1
Outdoor
Dis.
Coil En­
+10
tering
psig
Air Temp
65_F
265
75_F
302
85_F
343
95_F
388
105_F
441
115_F
494
Circuit 1
Outdoor
Dis.
Coil En­
+10
tering
psig
Air Temp
65_F*
248
75_F
285
85_F
328
95_F
374
105_F
425
115_F
479
LG/LC Series 180H Reheat
Circuit 1
Outdoor
Dis.
Coil En­
+10
tering
psig
Air Temp
65_F*
258
75_F
295
85_F
338
95_F
384
105_F
435
115_F
488
Outdoor
Coil En­
Dis. +10
tering
psig
Air Temp
65_F
246
75_F
282
85_F
324
95_F
368
105_F
407
115_F
461
Page 36
TABLE 10
Circuit 2
Suc.
Dis.
Suc.
+5
+10
+5
psig
psig
psig
134
273
135
138
311
138
140
352
140
143
397
142
147
448
144
149
500
145
TABLE 11
LG/LC Series 180H Std.
Circuit 2
Suc.
Dis.
Suc.
+5
+10
+5
psig
psig
psig
137
257
135
139
294
137
143
336
139
146
383
141
148
433
144
151
488
147
TABLE 12
Circuit 2
Suc.
Dis.
Suc.
+5
+10
+5
psig
psig
psig
136
267
133
138
304
135
142
346
137
145
393
139
147
443
142
150
498
145
TABLE 13
LG/LC Series 180U
Circuit 1
Circuit 2
Suc. +5
Dis. +10
psig
psig
135
256
138
293
140
336
142
387
145
421
148
475
Circuit 3
Dis.
Suc.
+10
+5
psig
psig
273
140
311
144
353
146
398
148
449
150
502
152
Circuit 3
Dis.
Suc.
+10
+5
psig
psig
259
137
296
137
338
140
385
144
435
147
488
151
Circuit 3
Dis.
Suc.
+10
+5
psig
psig
259
137
296
137
338
140
385
144
435
147
488
151
Suc. +5
psig
136
139
142
145
147
151