W
TM
AquaBalance
8 Vent termination requirements
The vent termination must be located to meet all requirements below (also applies to vertical vent terminations). The minimum distance
Figure 23
from adjacent public walkways, adjacent buildings, openable windows and building in the National Fuel Gas Code, ANSI Z223.1/NFPA
54 - latest edition and/or the Natural Gas and Propane Installation Code, CAN/CSA B149.1. The vent termination clearances below are
for U.S.A., for Canadian vent termination clearances please refer to the requirements of CAN/CSA B149.1 Natural Gas and Propane
Installation Code. Consideration should be given to avoid possible damage caused by vent plumes and condensate when choosing a
YHQWLQJ FRQ¿JXUDWLRQ DQG ORFDWLRQ 0DLQWDLQ D PLQLPXP FOHDUDQFH RI IW P KRUL]RQWDOO\ IURP DQG LQ QR FDVH DERYH RU EHORZ XQOHVV
D IW P KRUL]RQWDO GLVWDQFH LV PDLQWDLQHG IURP HOHFWULFDO PHWHUV JDV PHWHUV UHJXODWRUV DQG UHOLHI HTXLSPHQt.
Part number 550-100-305/0118
M
-
ALL
OUNT GAS
FIRED WATER BOILER
—
Boiler Manual
21