21 Field wiring
Outdoor temperature sensor Central Heating Boilers
(optional for Combi Boilers)
Outdoor sensor uses the back connection block,
Item
138, (right side of block ... terminals 5 and 6).
Recommended wire size 22 AWG (2-conductor shielded thermo-
stat wire 22 gauge).
Mount on north exterior wall,
flow of heat or cooling from other sources, approximately 10 feet
above ground level.
Do NOT run sensor wires with other electrical wires.
The Outdoor sensor must be installed unless specifical-
ly exempted in the Energy Act statement on page 131.
Figure 64
Outdoor sensor optional for Combi boiler.
Wiring the Indirect Tank Aquastat
Wiring the indirect tank aquastat to the Heating Only Boiler, will fire the
boiler to provide heated boiler water to the indirect tanks heating coil.
• Field supplied; zone panel, with priority zone, indirect circulator,
zone valve for indirect tank.
• Connect indirect aquastat N/O contact wires to boiler connections
#7 and #8, see Figure 65 below.
• Boiler must be in the "comfort mode" (not "eco" mode) push eco/
comfort button to exit "eco" mode, display will Not show "eco"
on display when in correct mode, when using an Indirect Water
Heater Tank.
Figure 65
Indirect tank aquastat connections
Part number 550-100-305/0118
M
-
ALL
OUNT GAS
FIRED WATER BOILER
(continued)
see Figure 62,
shielded from direct sunlight or
Indirect tank aquastat
(N/O) wire connection
points, pins 7 and 8
Boiler Manual
Wiring the Circulators (Heating Only Boiler)
The control of the Heating Only model of the boiler is ca-
pable of managing two (2) separate circulators, one for the
Heating circuit and one for the Domestic Hot water circuit.
The connections are located on the rear part of the con-
trol case. In order to access the connector you will have to
unscrew the screw located on the lower right corner of the
control to enable you to rotate the control and access the
connectors. See Figure 66 and Figure 67.
Figure 66
Circulator connectors (Heating Only
boilers)
Figure 67
Circulator connectors detail
In Figure 67, terminals 9, 10 and 11 (Item 32) are for con-
necting the Heating circuit circulator.
Terminals 11, 12, and 13 (Item 130) are for connecting the
Domestic Hot water circuit circulator.
The common terminal 11 is ground.
Only one circulator may be wired to each con-
nection point.