18 Multiple boiler installations
Figure 53
Side-to-side mounting of multiple boilers
Placing multiple boilers
1. Locate multiple boilers with spacings shown in Figure 53.
2. Provide indicated clearances around boilers for access and ser-
vicing. If recommended dimensions are not possible, provide
at least the minimum clearances given on page 5. Also follow
local codes.
3. Provide a minimum 36-inch walkway in front of the boilers to
ensure accessibility.
4. Unpack, assemble and mount boilers according to instructions
in this manual.
5. Provide clearance for installation of venting, air piping, gas pip-
ing, expansion tank, primary circulator and other accessories.